Changing event alerts:
You can change event alerts on the SNMP Trap Receivers page.
To configure the PDU+ to send e-mail or SNMP trap alerts to specified users when specific events occur,
complete the following steps:
1.
From the main status page, in the left navigation pane, click
System
.
2.
Click
Trap Receivers
to create a list of users or workstations who will be alerted with an SNMP trap
message. You can specify the IP addresses of up to eight trap receivers, the community information,
type of trap, severity of trap, and description of the events that cause the traps.
3.
Click
Email Notification
under
System
to create a list of up to four users who will be alerted with an
e-mail. Use this menu to specify the mail server, user account, DNS, and other information necessary
to set up a mail server for sending mail alerts. Use the Email Receivers Table to add the e-mail
addresses.
Changing the network information:
Use the Network menu to change the network information for the PDU+, for example, the IP address.
Changing the network configuration:
You can view or change the network configuration on the Network Configuration page.
To view or change the network configuration of the PDU+, complete the following steps:
1.
From the main status page, in the left navigation pane, click
Network
.
2.
Click
Configuration
to set the PDU+ IP address, gateway address, subnet mask, and Domain Name
System (DNS) address.
3.
Click
Control
to configure TCP/IP settings.
4.
Click
Access Control
to set access control to prevent unauthorized users from accessing the PDU+.
History and event log summaries:
The Logs menu provides a detailed description of all events and a record of the PDU+ status. System
administrators can use this page to analyze problems with network equipment.
Viewing the history log:
You can view the complete history of the PDU+ inputs and outputs on the History Log page.
To view the history of the PDU+, complete the following steps:
1.
From the main status page, in the left navigation pane, click
Logs
.
2.
Click
History
. Each event log file shows the time, date, and description of all the events occurring on
the PDU+.
Viewing the event log:
You can view the complete record of the PDU+ events on the Event Log page.
To view the complete record of the PDU+ events, complete the following steps:
1.
From the main status page, in the left navigation pane, click
Logs
.
2.
Click
Events
. Each log file shows a record of the input power and output power of each outlet.
Racks and rack features
49
Summary of Contents for 7014-T42
Page 1: ...Power Systems Racks and rack features ...
Page 2: ......
Page 3: ...Power Systems Racks and rack features ...
Page 6: ...iv Power Systems Racks and rack features ...
Page 72: ...60 Power Systems Racks and rack features ...
Page 73: ......
Page 74: ... Printed in USA ...