Installing a heat-sink retention module
Use this information to install a heat-sink retention module.
Before you begin
Read the safety information in “Safety” on page vii and “Installation guidelines”
on page 34.
If you are replacing a component or installing an optional device in the server, you
need to turn off the server and peripheral devices, and disconnect the power cords
and all external cables.
About this task
To install a heat-sink retention module, complete the following steps.
Procedure
1.
Carefully turn the server on its side so that it is lying flat, with the cover facing
up.
Attention:
Do not allow the server to fall over.
2.
Unlock and remove the left-side cover (see “Removing the left-side cover” on
page 39).
3.
Remove the air baffle (see “Removing the air baffle” on page 210).
4.
Align the retention module with the holes on the system board.
5.
Use a screwdriver to install the four screws.
6.
Install the heat sink (see “Installing a microprocessor and heat sink” on page
319).
Attention:
Make sure that you install each heat sink with its paired
microprocessor.
7.
Install the air baffle (see “Installing the air baffle” on page 211).
8.
Install and lock the left-side cover (see “Installing the left-side cover” on page
205).
What to do next
If you have replaced a component or installed an optional device in the server, you
need to reconnect the power cords and all external cables, and turn on the server
and peripheral devices.
Chapter 6. Removing and replacing components
335
Summary of Contents for 7383
Page 1: ...System x3500 M4 Type 7383 Installation and Service Guide ...
Page 2: ......
Page 3: ...System x3500 M4 Type 7383 Installation and Service Guide ...
Page 8: ...vi System x3500 M4 Type 7383 Installation and Service Guide ...
Page 42: ...24 System x3500 M4 Type 7383 Installation and Service Guide ...
Page 200: ...182 System x3500 M4 Type 7383 Installation and Service Guide ...
Page 360: ...342 System x3500 M4 Type 7383 Installation and Service Guide ...
Page 416: ...398 System x3500 M4 Type 7383 Installation and Service Guide ...
Page 470: ...452 System x3500 M4 Type 7383 Installation and Service Guide ...
Page 479: ...Taiwan Class A compliance statement Notices 461 ...
Page 480: ...462 System x3500 M4 Type 7383 Installation and Service Guide ...
Page 487: ......
Page 488: ... Part Number 46W8192 Printed in USA 1P P N 46W8192 ...