• (For fixed drawers.) This drawer is a fixed drawer and must not be moved for servicing unless specified by the manufacturer.

Attempting to move the drawer partially or completely out of the rack might cause the rack to become unstable or cause the

drawer to fall out of the rack. (R001 part 2 of 2)

DANGER: When working on or around the system, observe the following precautions:
Electrical voltage and current from power, telephone, and communication cables are hazardous. To avoid a shock hazard:
• If IBM supplied the power cord(s), connect power to this unit only with the IBM provided power cord. Do not use the IBM

provided power cord for any other product.

• Do not open or service any power supply assembly.
• Do not connect or disconnect any cables or perform installation, maintenance, or reconfiguration of this product during an

electrical storm.

• The product might be equipped with multiple power cords. To remove all hazardous voltages, disconnect all power cords.

– For AC power, disconnect all power cords from their AC power source.
– For racks with a DC power distribution panel (PDP), disconnect the customer’s DC power source to the PDP.

• When connecting power to the product ensure all power cables are properly connected.

– For racks with AC power, connect all power cords to a properly wired and grounded electrical outlet. Ensure that the outlet

supplies proper voltage and phase rotation according to the system rating plate.

– For racks with a DC power distribution panel (PDP), connect the customer’s DC power source to the PDP. Ensure that the

proper polarity is used when attaching the DC power and DC power return wiring.

• Connect any equipment that will be attached to this product to properly wired outlets.
• When possible, use one hand only to connect or disconnect signal cables.
• Never turn on any equipment when there is evidence of fire, water, or structural damage.
• Do not attempt to switch on power to the machine until all possible unsafe conditions are corrected.
• Assume that an electrical safety hazard is present. Perform all continuity, grounding, and power checks specified during the

subsystem installation procedures to ensure that the machine meets safety requirements.

• Do not continue with the inspection if any unsafe conditions are present.
• Before you open the device covers, unless instructed otherwise in the installation and configuration procedures: Disconnect the

attached AC power cords, turn off the applicable circuit breakers located in the rack power distribution panel (PDP), and

disconnect any telecommunications systems, networks, and modems.

DANGER:
• Connect and disconnect cables as described in the following procedures when installing, moving, or opening covers on this

product or attached devices.
To Disconnect:
1. Turn off everything (unless instructed otherwise).
2. For AC power, remove the power cords from the outlets.
3. For racks with a DC power distribution panel (PDP), turn off the circuit breakers located in the PDP and remove the power

from the Customer's DC power source.

4. Remove the signal cables from the connectors.
5. Remove all cables from the devices.
To Connect:
1. Turn off everything (unless instructed otherwise).
2. Attach all cables to the devices.
3. Attach the signal cables to the connectors.
4. For AC power, attach the power cords to the outlets.
5. For racks with a DC power distribution panel (PDP), restore the power from the Customer's DC power source and turn on the

circuit breakers located in the PDP.

6. Turn on the devices.
Sharp edges, corners and joints may be present in and around the system. Use care when handling equipment to avoid cuts,

scrapes and pinching. (D005)

DANGER: DANGER: Racks with a total weight of > 227 kg (500 lb.), Use Only Professional Movers! (R003)
DANGER: Do not transport the rack via fork truck unless it is properly packaged, secured on top of the supplied pallet. (R004)
CAUTION:
• Rack is not intended to serve as an enclosure and does not provide any degrees of protection required of enclosures.
• It is intended that equipment installed within this rack will have its own enclosure.
(R005)

Summary of Contents for 7965-S42

Page 1: ... PDP turn off the circuit breaker that controls the power to the system unit s or disconnect the customer s DC power source when directed to disconnect power during servicing Connect all devices installed in a rack cabinet to power devices installed in the same rack cabinet Do not plug a power cord from a device installed in one rack cabinet into a power device installed in a different rack cabine...

Page 2: ...il all possible unsafe conditions are corrected Assume that an electrical safety hazard is present Perform all continuity grounding and power checks specified during the subsystem installation procedures to ensure that the machine meets safety requirements Do not continue with the inspection if any unsafe conditions are present Before you open the device covers unless instructed otherwise in the i...

Page 3: ...grees When the rack cabinet is in the new location complete the following steps Lower the four leveling pads Install stabilizer brackets on the rack cabinet or in an earthquake environment bolt the rack to the floor If you removed any devices from the rack cabinet repopulate the rack cabinet from the lowest position to the highest position If a long distance relocation is required restore the rack...

Page 4: ... holes in the lower frame or stabilizer bracket by using the two bolts and washers that you removed from the rack and pallet Rear If needed for various local building codes bolt the rear of the rack to the floor surface through the holes in the lower rear of the frame by using the two bolts and washers that you removed from the rack and pallet Attaching rack in a suite 1 Where the two racks come t...

Page 5: ...built in extendable outriggers with small floating supplemental casters as motion anti tip features They must all be extended into a latched position before and during cabinet movement or relocation These native built in outriggers must not be removed completely but rather recessed in when finished to ensure they are readily available for future use C050 The equipment shall be installed or service...

Page 6: ...POWER9 processor and to all associated models Printed in USA Copyright International Business Machines Corporation 2020 US Government Users Restricted Rights Use duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp GI11 9939 00 1P P N 03GM113 ...