Table 129. Supported PDU power cords for POWER8 systems
Feature
code
(FC)
Description
v
Voltage
v
Amperage
v
Phase
v
Length
v
Wall plug
IBM
shipped
plug
View of
plug
Matched
female
connector
(on cord)
Matched
female wall
receptacle
(on wall)
IBM part
number
Countries
6489
Power cord, PDU to
wall
v
230 V ac output
v
32 A
v
3 phase wye
v
4.3 m (14 ft)
v
IEC 309, 3P+N+G
Plug type
532P6W
Connector
type
532C6W
Receptacle
type
532R6W
39M5413
Europe,
Middle East,
Africa
(EMEA)
6491
Power cord, PDU to
wall
v
230 V ac
v
63 A
v
Single phase
v
4.3 m (14 ft)
v
IEC 309, P+N+G
Plug type
363P6W
Connector
type
363C6W
Receptacle
type
363R6W
39M5415
Europe,
Middle East,
Africa
(EMEA)
6492
Power cord, PDU to
wall
v
200 - 208 V ac or 240
V ac
v
60 A plug (48 A
derated)
v
Single phase
v
4.3 m (14 ft)
v
IEC 309, 2P+G
Plug type
360P6W
Connector
type
360C6W
Receptacle
type
360R6W
39M5417
United
States,
Canada,
Latin
America,
Japan, and
Taiwan
6653
Power cord, PDU to
wall
v
230 V ac output
v
16 A
v
3 phase wye
v
4.3 m (14 ft)
v
IEC 309, 3P+N+G
Plug type
516P6W
Connector
type
516C6W
Receptacle
type
516R6W
39M5412
Switzerland
6654
Power cord, PDU to
wall
v
200 - 208 V ac or 240
V ac
v
30 A plug (24 A
derated)
v
Single phase
v
4.3 m (14 ft)
v
NEMA L6-30
Plug type
NEMA
L6-30P
Receptacle
type NEMA
L6-30R
39M5416
United
States,
Canada,
Latin
America,
Japan, and
Taiwan
106
Site and hardware planning
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...