Table 18. Temperature requirements
Operating
Nonoperating
10°C - 38°C (50°F - 100.4°F)
1
-40°C - 60°C (-40°F - 140°F)
1
The maximum 38°C (100.4°F) temperature must be derated 1°C (1.8 °F) per 137 m (450 ft) above 1295 m (4250 ft).
Table 19. Environmental requirements
Environment
Operating
Nonoperating
Maximum altitude
Noncondensing humidity
20% - 80% (allowable)
40% - 55% (recommended)
8% - 80% (including
condensing)
2134 m (7000 ft) above sea
level
Wet bulb temperature
21°C (69.8°F)
27°C (80.6°F)
Table 20. Noise emissions
1
Properties
Operating
Idle
L
WAd
6.0 bels
6.0 bels
L
pAm
(1-meter bystander)
43 dB
43 dB
1
Single drawer in standard 19-inch rack with 24 hard drives, nominal environmental conditions, and no front or rear
doors on rack.
For a description of noise emission values, see Acoustics.
All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.
Table 21. Service clearances for rack-mounted expansion unit
Front
Back
Sides
914 mm (36 in.)
914 mm (36 in.)
914 mm (36 in.)
Side and top clearances are optional during operation.
Safety compliance:
This hardware is designed and certified to meet the following safety standards: UL
60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences
EMX0 PCIe Gen3 I/O expansion drawer (feature code EMX0)
Hardware specifications provide detailed information for your expansion unit, including dimensions,
electrical, power, temperature, environment, and service clearances.
Table 22. Dimensions for rack-mounted expansion unit
Width
Depth
Height
Weight (maximum)
482 mm (19 in.)
802 mm (31.6 in.)
173 mm (6.8 in.), 4 EIA
units
54.4 kg (120 lb)
Table 23. Electrical
1,2,3
Electrical characteristics
Properties
AC rated voltage and frequency
100 - 127 V ac or 200 - 240 V ac at 50 or 60 Hz plus or
minus 3 Hz (FC EMXA)
DC rated voltage
192 - 400 V dc (FC EMXB)
Thermal output (maximum)
1740 BTU/hr
Maximum power consumption
510 W
Maximum kVA
0.520
Site and hardware planning
15
Summary of Contents for 8408-44E
Page 1: ...Power Systems Site and hardware planning IBM...
Page 2: ......
Page 3: ...Power Systems Site and hardware planning IBM...
Page 16: ...xiv Site and hardware planning...
Page 18: ...2 Site and hardware planning...
Page 22: ...6 Site and hardware planning...
Page 51: ...Figure 19 Model 0555 and 7014 S25 plan view Site and hardware planning 35...
Page 192: ...176 Site and hardware planning...
Page 204: ...188 Site and hardware planning...
Page 205: ......
Page 206: ...IBM Printed in USA...