Table 31. Electrical
Electrical characteristics
Properties
kVA (maximum)
1.684
Rated voltage and frequency
200 - 240 V ac at 50 - 60 plus or minus 0.5 Hz
Thermal output (maximum)
5461 Btu/hr
Power requirements (maximum)
1600 W
Power factor
0.95
Inrush current
80 A
Leakage current (maximum)
3.5 mA
Phase
1
Table 32. Service clearance
Front
Back
Sides
Top
762 mm (30 in.)
762 mm (30 in.)
762 mm (30 in.)
762 mm (30 in.)
Side and top clearances are optional when operating.
Table 33. Feature code
Feature Code
Top rack specify
Bottom rack specify
PDU support
Power cords
0550
1
None
None
0 to 4
2
Model 9406-830
3
, PDU
1
Ten EIA units of space not managed by the configurator.
2
Feature codes 5160, 5161, and 5162.
3
Model 9406-830 does not plug into a power distribution unit.
Model 0551 rack
The 0551 rack specifications provide detailed information for your rack.
The 0551 provides an empty 1.8 m rack (36 EIA units of total space).