Installing the server
Complete the following procedure to install the server into the rack enclosure.
1. Mount the server on the slide rails.
a. Extend the slide rails until they lock into place.
b. Position the server horizontally, with the LED panel at the left.
c. Align the inner slides on the sides of the server with the slide rails; then,
slide the server onto the outer slide about 5 cm (2 in.), until the server
stops.
d. Press the safety latches
.1/
on the slide rails and slide the server further
onto the outer slide, until the slide rails click into place.
e. Press the safety latches
.1/
on the slide rails again and slide the server
part of the way into the rack enclosure.
Note: When the server is fully extended, safety latches on the slide rails
lock into place. This prevents the server from being accidentally
pulled out too far and dropped. To release the safety latch, press
in.
18
Netfinity
4000R User's Handbook
Summary of Contents for 865263Y - Netfinity 4000R - 8652
Page 1: ...IBM IBM Netfinity 4000R User s Handbook ...
Page 2: ......
Page 3: ...IBM IBM Netfinity 4000R User s Handbook ...
Page 12: ...2 Netfinity 4000R User s Handbook ...
Page 32: ...22 Netfinity 4000R User s Handbook ...
Page 38: ...28 Netfinity 4000R User s Handbook ...
Page 48: ...38 Netfinity 4000R User s Handbook ...
Page 76: ...66 Netfinity 4000R User s Handbook ...
Page 81: ...Section 3 Appendixes Copyright IBM Corp 1999 71 ...
Page 82: ...72 Netfinity 4000R User s Handbook ...
Page 86: ...76 Netfinity 4000R User s Handbook ...
Page 88: ...78 Netfinity 4000R User s Handbook ...
Page 98: ...88 Netfinity 4000R User s Handbook ...
Page 102: ...IBM Part Number 09N7703 Printed in U S A ð9N77ð3 ...