2. Connect the other line cord to the Backup inlet on the Rack PDU. Use the line
cord that you will connect to your backup power source.
3. Remove the screws on the cable clamps and route the line cords through the
clamps; then, reinstall the screws on the cable clamps and repeat step 1 and
step 2 for the other device, if you installed two devices.
4. Route the line cords left or right, toward the side of the rack cabinet; then, route
the line cords along the side brace towards the back of the rack cabinet and
secure them with the cable straps that come with this option.
5. Route each line cord toward a dedicated independent power source, such as a
UPS or electrical outlet. Use the provided cable straps to secure the line cords
along the way. Use the openings in your rack cabinet, if you must exit the rack
cabinet to connect to your power source.
6. After you connect both line cords to properly wired and grounded dedicated
independent power sources, you can connect one server (having up to four line
cords) to the four power outlets on the Rack PDU. Route all other power cables
neatly, and use cable straps to secure the cables that you plug into the outlets
on the Rack PDU.
Figure 71. Connecting and routing the line cords
166
Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Summary of Contents for 9306
Page 1: ...Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 2: ......
Page 3: ...Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 10: ...viii Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 14: ...4 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 19: ...Figure 4 Expansion NetBAY42 Rack cabinet without side panels Type 9306 Model 250 420 421 9...
Page 40: ...30 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 64: ...54 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 67: ...Extension Rack Model 42X NetBAY 42 Enterprise Rack Type 9308 Models 42P 42X 4SA 4SB 42S 42E 57...
Page 68: ...Primary Rack 42S 58 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 87: ...Note The maximum server weight is 77 kg 170 lb NetBAY3 enclosure 77...
Page 90: ...Front cover 80 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 94: ...84 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 108: ...98 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 109: ...Parts listing Type 9306 Model OPT 1 2 2 3 1U Flat Panel Monitor Console Kit 99...
Page 200: ...190 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 203: ...1 DANGER 2 DANGER 3 DANGER 4 DANGER Related service information 193...
Page 207: ...1 2 3 4 Related service information 197...
Page 215: ...Related service information 205...
Page 216: ...206 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 217: ...Related service information 207...
Page 218: ...208 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 219: ...Related service information 209...
Page 220: ...210 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 221: ...Related service information 211...
Page 231: ...Related service information 221...
Page 232: ...222 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 233: ...Related service information 223...
Page 234: ...224 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 235: ...Related service information 225...
Page 236: ...226 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Page 243: ......
Page 244: ...Part Number 10K2658 1P P N 10K2658...