Fans
Before performing the following procedure, read “Safety Notices” on page vii.
Removing a Processor Fan in a Non-Hot-Swap Environment
Note: A processor fan in a non-hot-swap environment means that your system is
configured at the factory with one processor fan installed. To put your system
into an environment that enables the hot-swapping of the processor fans, you
must purchase a second processor fan and insert it into the unused docking
connector. It is not necessary to shut down the system when adding the second
processor fan.
To remove a processor fan in a non-hot-swap environment, do the following:
1. On a Model 6C4, open the front and rear rack doors and put the system into the
service position as described in “Placing the Model 6C4 into the Service Position”
On a Model 6E4, open the bezel door.
2. If the system is not in the standby state, shut down the system as described in
“Stopping the System” on page 52.
92
Eserver
pSeries 630 Model 6C4 and Model 6E4 Installation Guide
Summary of Contents for @Server pSeries 630 6C4
Page 1: ...pSeries 630 Model 6C4 and Model 6E4 Installation Guide SA38 0605 01 ERserver IBM...
Page 2: ......
Page 3: ...pSeries 630 Model 6C4 and Model 6E4 Installation Guide SA38 0605 01 ERserver IBM...
Page 12: ...x Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 14: ...xii Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 22: ...6 Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 64: ...48 Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 148: ...132 Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 152: ...136 Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 156: ...140 Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 166: ...150 Eserver pSeries 630 Model 6C4 and Model 6E4 Installation Guide...
Page 179: ......
Page 180: ...IBMR Part Number 00P3937 Printed in U S A August 2002 SA38 0605 01 1P P N 00P3937...