Installing
the
environmental
monitoring
probe
To
install
the
environmental
monitoring
probe,
complete
the
following
steps:
1.
If
applicable,
connect
external
contact
closure
inputs
to
the
screw
terminals
on
the
environmental
monitoring
probe.
Environmental
monitoring
probe screw
terminals
Pin 1
Note:
Contact
closure
device
1
is
connected
between
pins
1
and
2.
Device
2
is
connected
between
pins
3
and
4
(as
labeled
to
show
device
1
and
2).
Contact
closure
devices
can
be
normally
open
or
normally
closed.
Table
3.
Environmental
monitoring
probe
screw
terminal
pin
assignment
Pin
number
Description
Normally
open/
normally
closed
1
Contact
1
return
Normally
closed
2
Contact
1
signal
input
Normally
open
3
Contact
2
return
Normally
closed
4
Contact
2
signal
input
Normally
open
2.
Connect
the
CAT5
network
cable
that
comes
with
the
PDU
to
the
environmental
monitoring
probe
RJ-45
connector
and
to
the
RJ-45
console
connector
on
the
PDU.
Note:
If
the
cable
is
not
long
enough
for
your
configuration,
you
can
use
a
cable
that
is
20
m
(65.6
ft)
or
less.
LA
N
Ethernet cable
RJ-45
console
connector
RJ-45
connector
PDU
Environmental
monitoring
probe
1
2
3
4
5
6
3.
Make
sure
that
the
PDU
has
a
network
connection,
the
power
cord
is
connected,
and
the
PDU
is
turned
on.
The
environmental
monitoring
probe
is
automatically
recognized
by
the
PDU.
38
DPI
C13
PDU+,
DPI
C19
PDU+,
and
DPI
C19
3-phase
PDU+:
Installation
and
Maintenance
Guide
Summary of Contents for DPI C13 PDU+
Page 1: ...DPI C13 PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide...
Page 2: ......
Page 3: ...DPI C13 PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide...
Page 20: ...8 DPI C13 PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide...
Page 28: ...16 DPI C13 PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide...
Page 48: ...36 DPI C13 PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide...
Page 54: ...42 DPI C13 PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide...
Page 58: ...46 DPI C13 PDU DPI C19 PDU and DPI C19 3 phase PDU Installation and Maintenance Guide...
Page 87: ......
Page 88: ...Part Number 40K9635 Printed in USA 1P P N 40K9635...