4
IBM Power System E850C: Technical Overview and Introduction
Figure 1-2 shows the Power E850C rear view.
Figure 1-2 Rear view of Power E850C server
1.2 Operating environment
Table 1-1 details the operating environment for the Power E850C server.
Table 1-1 Operating environment for Power E850C
Power E850C operating environment
System
Power E850C
Operating
Non-operating
Temperature
Recommended
18 - 27° C (64 - 80° F)
1 - 60° C (34 - 140° F)
Allowable
5 - 40° C (41 - 104° F)
Relative humidity
8 - 80%
5 - 80%
Maximum dew point
24° C (75° F)
27° C (80° F)
Operating voltage
200 - 240 V ac
180 - 400 V dc
N/A
Operating frequency
50 - 60 Hz +/- 3 Hz ac
N/A
Maximum power consumption
3,850 Watts
N/A
Maximum power source
loading
3.90 kVA
N/A
Maximum thermal output
13,140 BTU/hour
N/A
Maximum altitude
3,050 m (10,000 ft.)
N/A