Figure 6. Sample illustration to show space around the rack
For a Model 092 expansion enclosure, use the recommended measurements that are given in Table 11 on
Table 11. Service clearance requirements
Front
1
Back
1200 mm (47 in.)
1000 mm (39 in.)
1
Storage racks require larger service clearances in the front of the rack.
For more information on the layout of the room, see Computer room layout
See Site preparation and physical planning section to help you prepare your physical site for the
installation of a Model 092 expansion enclosure.
Additional space requirements
Ensure that these additional space requirements, as shown in Table 12 on page 30, are available around
the enclosures.
Table 12. Clearances
Location
Additional space requirements
Reason
Left and right sides
50 mm (2 in.)
Cooling air flow
Back
Minimum: 100 mm (4 in.)
Cable exit
30 IBM Elastic Storage System 5000: Model 092 Hardware Guide
Summary of Contents for Elastic Storage System 5000 Series
Page 1: ...IBM Elastic Storage System 5000 Version 6 0 1 Model 092 Hardware Guide IBM SC28 3135 00...
Page 8: ...viii...
Page 10: ...24 Enclosure models and rack requirements 74 x...
Page 14: ...xiv IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Page 32: ...18 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Page 36: ...22 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Page 51: ...Figure 11 Cable connectivity from I O servers Chapter 4 Planning for hardware 37...
Page 86: ...72 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Page 90: ...76 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Page 98: ...84 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Page 100: ...86 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Page 101: ......
Page 102: ...IBM Product Number 5765 DME 5765 DAE SC28 3135 00...