DANGER
Overloading an electrical circuit breaker is potentially a fire
hazard and a shock hazard under certain conditions. To
avoid these hazards, adhere to the instructions in the
following statements.
a. If you are connecting to a 100–127 V ac power source,
connect each power cord to a separate branch circuit.
b. If you are connecting to a 200–240 V ac power source
and the branch circuit breaker rating is:
1) 13 amps or less, connect each power cord to a
separate branch circuit.
2) 14 amps to 19 amps, do not connect more than two
power cords to the same branch circuit.
3) 20 amps or greater, you may connect up to three
power cords to the same branch circuit.
5. If you disconnected any cables or power cords from the back of the server,
reconnect the cables; then, plug the power cords into properly grounded
electrical outlets.