Reference Code
Description/Action Perform all actions before exchanging Failing Items
Failing Item
8930
Integrated Netfinity Adapter fault
8940 to 8943
External Netfinity Server R485 Communication fault
8A00
SPCN Configuration mismatch
9012
Address not valid.
LIC command had a frame address that was not valid.
Exchange the SPCN frame-to-frame cables to the failing frame.
9013
Invalid Node Address.
The address in the SPCN command does not match the secondary nodes
assigned address.
Exchange the failing items for the SPCN node reporting the error.
9014
A command has an invalid address mode.
A command from the system unit specified a unit address of D or E or had
a frame address of 00.
Exchange the failing items in the system unit.
AJDG301
TWRCARD
9016, 9021
A command to an SPCN node was rejected.
No action required. This reference code is logged for information only.
9022
Addressed Unit not in frame.
The addressed unit does not exist in the addressed frame.
No action required. This reference code is logged for information only.
9023
Addressed Unit exists, but the frame is powered off.
The addressed unit is in a frame that is powered off.
No action required. This reference code is logged for information only.
9024
SPCN Licensed Internal Code not valid.
The Licensed Internal Code in one of the secondary nodes is not valid. The
code will be reloaded.
No action required. This reference code is logged for error analysis only.
9025
SPCN Licensed Internal Code is not valid.
The Licensed Internal Code in one of the frames is not valid. The code will
be reloaded.
No action required. This reference code is logged for error analysis only.
9026
Battery Power Unit is reporting a low charge.
The battery power unit is not charged enough to run a test.
No action required. This reference code is logged for information only.
9027
Battery Power Unit is defective.
No action required. This reference code is logged for information only.
1xxx
System Reference Codes