Four PDUs can be mounted vertically in the back of the T00 and T42 racks. Figure 1-10
shows placement of the four vertically mounted PDUs. In the rear of the rack, two additional
PDUs can be installed horizontally in the T00 rack and three in the T42 rack. The four vertical
mounting locations will be filled first in the T00 and T42 racks. Mounting PDUs horizontally
consumes 1U per PDU and reduces the space available for other racked components. When
mounting PDUs horizontally, the best approach is to use fillers in the EIA units that are
occupied by these PDUs to facilitate proper air-flow and ventilation in the rack.
Figure 1-10 PDU placement and PDU view
The PDU receives power through a UTG0247 power-line connector. Each PDU requires one
PDU-to-wall power cord. Various power cord features are available for various countries and
applications by varying the PDU-to-wall power cord, which must be ordered separately. Each
power cord provides the unique design characteristics for the specific power requirements. To
match new power requirements and save previous investments, these power cords can be
requested with an initial order of the rack or with a later upgrade of the rack features.
Rack Rear View
4
3
2
1
Circuit breaker reset
Status LED