34
IBM Power 750 and 760 Technical Overview and Introduction
Table 1-15 shows the available wall power cord options for the PDU and iPDU features, which
must be ordered separately.
Table 1-15 Power wall cord options for the PDU and iPDU features
The Universal PDUs are compatible with previous models.
To better enable electrical redundancy, each server has two power supplies that must be
connected to separate PDUs, which are not included in the base order. For maximum
availability, the best way is to connect power cords from the same system to two separate
PDUs in the rack, and to connect each PDU to independent power sources.
For detailed power requirements and power cord details, see the Planning for power section
in the IBM Power Systems Hardware Information Center website:
http://pic.dhe.ibm.com/infocenter/powersys/v3r1m5/topic/p7had/p7hadrpower.htm
1.13.6 Useful rack additions
This section highlights several solutions for IBM Power Systems rack-based systems.
IBM System Storage 7214 Tape and DVD Enclosure
The IBM System Storage® 7214 Tape and DVD Enclosure (Model 1U2) is designed to mount
in one EIA unit of a standard IBM Power Systems 19-inch rack and can be configured with
one or two tape drives, or either one or two Slim DVD-RAM or DVD-ROM drives in the bay on
the right side.
Feature
code
Wall plug
Rated
voltage (Vac)
Phase
Rated
amperage
Geography
6653
IEC 309,
3P+N+G, 16A
230
3
16 Amps
Internationally available
6489
IEC309
3P+N+G, 32A
230
3
24 Amps
EMEA
6654
NEMA L6-30
200-208, 240
1
24 Amps
US, Canada, LA, Japan
6655
RS 3750DP
(watertight)
200-208, 240
1
24 Amps
US, Canada, LA, Japan
6656
IEC 309,
P+N+G, 32A
230
1
24 Amps
EMEA
6657
PDL
230-240
1
24 Amps
Australia, New Zealand
6658
Korean plug
220
1
24 Amps
North and South Korea
6492
IEC 309,
2P+G, 60A
200-208, 240
1
48 Amps
US, Canada, LA, Japan
6491
IEC 309,
P+N+G, 63A
230
1
48 Amps
EMEA
Notes: Ensure that the appropriate power cord feature is configured to support the power
being supplied. Based on the power cord that is used, the PDU can supply from 4.8 kVA to
19.2 kVA. The power of all the drawers plugged into the PDU must not exceed the power
cord limitation.