Power775 Disk Enclosure Fan Service Procedure
22 of 61
Figure 12 Rear Enclosure ID LED is located on the bottom right side of the DE
STEP 10
Check the Enclosure VPD Label
Verify that the location codes of the Fans to be replaced match the enclosure VPD Label of the DE you have
identified (see Figure 5).
STEP 11
Turn off the Enclosure Identify LEDs of the DE by using the following command from the BPC FSP Command
Line:
This is the command syntax:
bpccmd –c 27<blank>0000<cage ID><FRU ID><LED blink state 00=off, 02=blink>
<blank>
= “11”
<cage ID>
= see table below
<FRU ID>
= “01” for the DE Identify LED.
<LED state>
= “00” for this step
Type in the following, inserting the correct cage ID DE chassis location:
bpccmd –c 27110000xx0100
Where “xx” is the cage ID of the DE you are replacing.
This field will be 05,07,09,0B,0D, or 0F (see Figure 6).
The correct return code is 001100. If you do not receive this, contact the next level of support.
Below is an example assuming Cage ID=0f