Attach
the
Rack
to
a
Low-Raised
or
High-Raised
Floor
Before
the
rack
can
be
attached
to
the
floor,
the
customer
must
do
the
following
1.
Cut
and
properly
place
the
floor
panels
2.
Install
eyebolts
in
the
floor,
and
install
the
frame
Cutting
and
Placement
of
Floor
Panels
This
section
provides
recommendations
for
making
the
necessary
openings
in
the
raised
floor
for
installing
the
pSeries
655.
The
numeric
grid
positions
shown
on
the
floor
tiles
in
the
illustration
are
used
to
identify
relative
positions
of
the
cutout
in
floor
tiles
that
may
be
cut
in
advance.
1.
Measure
the
tile
size
of
the
raised
floor.
2.
Verify
the
floor
tile
size.
The
floor
tile
size
illustrated
is
600
mm
(23.6
in.)
and
610
mm
(24
in.)
floor
tiles.
3.
Ensure
adequate
floor
space
is
available
to
place
the
frames
over
the
floor
tiles
exactly
as
shown
in
the
illustration.
For
front-to-back
and
side-to-side
clearances,
refer
to
″
Considerations
for
Multiple
System
Installations
″
in
the
Site
and
Hardware
Planning
Information
.
Use
the
plan
view
if
necessary.
Consider
all
obstructions
above
and
below
the
floor.
4.
Identify
the
floor
tiles
needed,
and
list
the
total
quantity
of
each
tile
required
for
the
installation.
5.
Cut
the
required
quantity
of
floor
tiles.
When
cutting
the
tiles,
you
must
adjust
the
size
of
the
cut
for
the
thickness
of
the
edge
molding
you
are
using.
The
dimensions
shown
in
the
illustration
are
finished
dimensions.
For
ease
of
installation,
number
each
floor
tile
as
it
is
cut,
as
shown
in
the
following
illustration.
Note:
Depending
on
the
floor
tile
type,
additional
tile
support
(using
pedestals)
may
be
required
to
restore
structural
integrity
of
floor
tiles
with
cutouts.
Consult
the
floor
tile
manufacturer
to
ensure
that
the
floor
tiles
can
sustain
a
concentrated
load
of
567
kg
(1250
lbs).
For
multiple
frame
installation,
it
is
possible
that
two
casters
will
produce
loads
as
high
as
1134
kg
(2500
lbs).
6.
Use
the
following
raised
floor
illustration
to
install
the
panels
in
the
proper
positions.
Notes:
a.
This
floor-tile
arrangement
is
recommended
so
that
the
casters
or
leveling
pads
are
placed
on
separate
floor
tiles
to
minimize
the
weight
on
a
single
floor
tile.
Furthermore,
it
is
recommend
that
floor
tiles
bearing
the
weight
(having
casters
or
leveling
pads
on
the
tiles)
be
uncut
to
retain
the
strength
of
the
floor
tile.
b.
The
following
illustration
is
intended
only
to
show
relative
positions
and
accurate
dimensions
of
floor
cutouts.
The
illustration
is
not
intended
to
be
a
machine
template
and
is
not
shown
to
scale.
146
Eserver
pSeries
655
Installation
Guide
Summary of Contents for pseries 655
Page 1: ...pSeries 655 Installation Guide SA38 0616 03 ERserver...
Page 2: ......
Page 3: ...pSeries 655 Installation Guide SA38 0616 03 ERserver...
Page 14: ...xii Eserver pSeries 655 Installation Guide...
Page 22: ...6 Eserver pSeries 655 Installation Guide...
Page 54: ...38 Eserver pSeries 655 Installation Guide...
Page 101: ...2 1 1 Top of Cassette 2 Handle Chapter 4 Installation and Removal Procedures 85...
Page 125: ...1 Metal EMC Shield 2 Adapter Bracket Chapter 4 Installation and Removal Procedures 109...
Page 128: ...112 Eserver pSeries 655 Installation Guide...
Page 132: ...116 Eserver pSeries 655 Installation Guide...
Page 156: ...140 Eserver pSeries 655 Installation Guide...
Page 204: ...188 Eserver pSeries 655 Installation Guide...
Page 211: ......
Page 212: ...Part Number 80P3836 Printed in USA February 2004 SA38 0616 03 1P P N 80P3836...