1
Simplified
UEPO
Front
Panel
7
J02
Connector
(White)
2
Simplified
UEPO
Side
Panel
8
Power
Switch
3
Simplified
UEPO
Rear
Panel
9
System
Fault
LED
4
J00
Connector
(Back)
10
Start
Service
Button
(Green)
5
J01
Connector
(Back)
11
Service
Complete
Button
(White)
6
Room
EPO
Bypass
Interlock
12
3-Dimensional
View
of
UEPO
Switch
c.
Install
the
external
cable,
if
required,
to
connector
J02
on
the
bottom
of
the
EPO
switch.
v
If
the
external
EPO
connection
is
installed,
the
internal
toggle
switch
is
mechanically
forced
into
the
ROOM
EPO
ACTV
position
(to
the
right).
v
If
there
is
no
external
EPO
cable,
manually
set
the
internal
toggle
switch
to
the
ROOM
EPO
BYPASS
position.
To
set
this
switch,
pull
the
knob
down
to
the
ROOM
EPO
BYPASS
position,
and
release
the
knob
(to
the
left).
d.
Ensure
that
the
red
UEPO
switch
is
on
(up
position).
e.
Switch
the
UEPO
BYPASS
switches
on
both
BPCs
back
to
NORMAL
mode.
f.
Press
the
Service
Complete
button
(white)
on
the
UEPO
switch
to
indicate
completion
of
this
procedure.
186
Eserver
pSeries
655
Installation
Guide
Summary of Contents for pseries 655
Page 1: ...pSeries 655 Installation Guide SA38 0616 03 ERserver...
Page 2: ......
Page 3: ...pSeries 655 Installation Guide SA38 0616 03 ERserver...
Page 14: ...xii Eserver pSeries 655 Installation Guide...
Page 22: ...6 Eserver pSeries 655 Installation Guide...
Page 54: ...38 Eserver pSeries 655 Installation Guide...
Page 101: ...2 1 1 Top of Cassette 2 Handle Chapter 4 Installation and Removal Procedures 85...
Page 125: ...1 Metal EMC Shield 2 Adapter Bracket Chapter 4 Installation and Removal Procedures 109...
Page 128: ...112 Eserver pSeries 655 Installation Guide...
Page 132: ...116 Eserver pSeries 655 Installation Guide...
Page 156: ...140 Eserver pSeries 655 Installation Guide...
Page 204: ...188 Eserver pSeries 655 Installation Guide...
Page 211: ......
Page 212: ...Part Number 80P3836 Printed in USA February 2004 SA38 0616 03 1P P N 80P3836...