Rear Fan
Removal
1. Open the rear door of the rack unit.
2. Reposition any cables that hinder access to the rear fan.
3. Using a finger nail, depress the tab on the fan plug and pull to remove the fan
cable from the bulkhead fan connector.
Notes:
a. The rubber isolators should remain in the bulkhead.
b. If both top isolators are damaged, the drawer must be placed in the rear
service position, as described in “Rear Service Position” on page 7-23, to
replace them.
c. If any of the rubber isolators are damaged, three of the four are sufficient to
hold the fan in position.
4. Carefully remove the fan from each of the four isolators that hold the fan to the
drawer.
Pull the fan away from the bulkhead.
Use a needle nose pliers to firmly grasp the rubber isolator between the fan
and the bulkhead.
7-22
RS/6000 Enterprise Server Model H50 Installation and Service Guide
Summary of Contents for RS/6000 H50
Page 1: ...RS 6000 Enterprise Server Model H50 IBM Installation and Service Guide SA38 0547 00...
Page 16: ...xvi RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 30: ...1 12 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 131: ...Chapter 3 Error Code to FRU Index 3 51...
Page 160: ...5 18 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 245: ...Chapter 8 Parts Information Chapter 8 Parts Information 8 1...
Page 290: ...B 4 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 305: ...expect 8 r or 7 r or 6 r or 4 r or 3 r delay 2 done Appendix C Modem Configurations C 15...
Page 312: ...C 22 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 316: ...D 4 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 324: ...X 8 RS 6000 Enterprise Server Model H50 Installation and Service Guide...
Page 326: ...X 10 RS 6000 Enterprise Server Model H50 Installation and Service Guide...