Figure 102. Replace fan module
Replacing all fan modules
3. Repeat steps “1” on page 90 and “2” on page 90 for each fan module to be replaced.
4. Power on the expansion enclosure.
Installing or replacing a fan interface board: 2145-92F
You can replace a fan interface board (FIB) in a 2145-92F expansion enclosure.
Before you begin
This task assumes that the following conditions are met:
• You removed the fan interface board, following the process described in “Removing a fan interface
board: 2145-92F ” on page 112.
• All power cables were removed from the enclosure, as described in “Powering off the expansion
enclosure: 2145-92F ” on page 129.
• The expansion enclosure is removed from the rack, as described in “Removing an expansion enclosure
from a rack: 2145-92F ” on page 94.
• A lift is supporting the weight of the enclosure.
• The top cover, fans, drives, and other heavy FRUs are removed from the enclosure.
About this task
The 2145-92F expansion enclosure contains two fan interface boards (FIBs). The FIBs act as the
interface between the fans and the system drive board. FIB 1 connects fan modules 1 and 2 to the drive
board; FIB 2 connects fan modules 3 and 4. If the fault LED on each fan module is lit, it is possible that
the FIB that controls those modules needs to be replaced. You can also issue the
lsenclosurefanmodule
command to display the status of the fans.
If you removed the FIBs from a faulty expansion enclosure, you must reinstall them in the replacement
enclosure. Refer to the procedure described in “Replacing an enclosure: 2145-92F ” on page 115.
Procedure
1. Assemble the new FIB, cover, and the cover screws (shown in Figure 103 on page 92) in a safe
location.
Chapter 4. Installing an optional 5U SAS expansion enclosure 91
Summary of Contents for SAN Volume Controller 2145-SV1
Page 1: ...IBM SAN Volume Controller Hardware Installation Guide IBM...
Page 6: ...vi...
Page 48: ...16 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 62: ...30 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 72: ...40 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 168: ...136 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 176: ...144 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 178: ...146 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 182: ...150 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 192: ...160 SAN Volume Controller Model 2145 SV1 Hardware Installation Guide...
Page 193: ......
Page 194: ...IBM...