Table 9. Event message and the device on which the fan is located (continued)
Event message
Physical fan location
Function
Numeric sensor "Fan 4A
Tach"
Host server fan 4
speed
Numeric sensor "Fan 5A
Tach"
Host server fan 5
speed
Numeric sensor "MEU Fan 1
Tach"
MAX5 fan 1
speed
Numeric sensor "MEU Fan 2
Tach"
MAX5 fan 2
speed
Numeric sensor "MEU Fan 3
Tach"
MAX5 fan 3
speed
Numeric sensor "MEU Fan 4
Tach"
MAX5 fan 4
speed
Numeric sensor "MEU Fan 5
Tach"
MAX5 fan 5
speed
Integrated management module (IMM) error messages
The following sections describe the IMM error messages and suggested actions to
correct the detected problems the server or the MAX5 memory expansion module.
For more information about IMM, see the
Integrated Management Module User's
Guide
at http://www.ibm.com/systems/support/supportsite.wss/
docdisplay?lndocid=MIGR-5079770&brandind=5000008.
Server IMM error messages
The following table describes the IMM error messages and suggested actions to
correct the detected server problems.
For IMM error messages that are generated when the MAX5 is attached to the
System x3690 X5 server, see “IMM error messages detected when a MAX5 is
attached to the server” on page 221.
Table 10. System x3690 X5 IMM error messages
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
v
See Chapter 4, “Parts listing, System x3690 X5 Types 7147, 7148, 7149, and 7192,” on page 249 to determine which components
are customer replaceable units (CRU) and which components are field replaceable units (FRU).
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a trained service
technician.
Event ID
Message
Severity
Description
Action
80010002-2801xxxx
Numeric sensor CMOS VBAT going
low (lower non-critical) has asserted.
Info
Sensor has reported
CMOS battery
power change from
normal to
non-critical state.
Information only; no action
is required.
80010202-0701xxxx
Numeric sensor Planar 5V going low
(lower critical) has asserted.
Error
A lower critical
sensor going low
has asserted.
(Trained service technician
only) Replace the system
board.
80010202-0701xxxx
Numeric sensor Planar 3.3V going low
(lower critical) has asserted.
Error
A lower critical
sensor going low
has asserted.
(Trained service technician
only) Replace the system
board.
80010202-2801xxxx
Numeric sensor Planar VBAT going
low (lower critical) has asserted.
Error
A lower critical
sensor going low
has asserted.
Replace the 3 V battery.
168
System x3690 X5 Types 7147, 7148, 7149, and 7192: Problem Determination and Service Guide
Summary of Contents for System x3690 X5
Page 1: ...System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 2: ......
Page 3: ...System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 8: ...vi System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 13: ...Safety statements Safety xi...
Page 22: ...4 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 266: ...248 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 278: ...260 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 386: ...368 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 407: ...1 2 Chapter 5 Removing and replacing components 389...
Page 444: ...426 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 454: ...436 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 461: ...weight of memory enclosure 28 Index 443...
Page 462: ...444 System x3690 X5 Types 7147 7148 7149 and 7192 Problem Determination and Service Guide...
Page 463: ......
Page 464: ...Part Number 47C8865 Printed in USA 1P P N 47C8865...