Specifications
The
uninterruptible
power
supply
includes
the
following
specifications.
Table
1.
UPS3000
LV
and
UPS3000
HV
specifications
UPS3000
LV
UPS3000
HV
Height
89
mm
(3.5
in.)
89
mm
(3.5
in.)
Width
482.6
mm
(19.0
in.)
482.6
mm
(19.0
in.)
Depth
622.3
mm
(24.5
in.)
622.3
mm
(24.5
in.)
Additional
clearance
25
mm
(0.98
in.)
for
circuit
breakers
3
mm
(0.12
in.)
for
outlets
25
mm
(0.98
in.)
for
circuit
breakers
3
mm
(0.12
in.)
for
outlets
Weight
37.0
kg
(82.0
lb)
37.0
kg
(82.0
lb)
Operating
temperature
at
0
to
3000
m
(0
to
10,000
ft)
0°to
40°C
(32°
to
104°F)
0°to
40°C
(32°
to
104°F)
Maximum
operating
altitude
2000
m
(6562
ft)
2000
m
(6562
ft)
Relative
humidity
0
to
95%
noncondensing
0
to
95%
noncondensing
Nominal
input
voltage
120
V
220
V
ac
(selectable
from
200-240
V
ac))
Maximum
input
current
30
amps
16
amps
Input
voltage
range
for
main
operations
90
to
144
V
160
to
288
V
Input
voltage
adjustable
range
for
main
operations
77
to
152
V
154
to
288
V
Nominal
output
voltage
120
V
220
V,
configurable
for
200,
220,
230,
or
240
V
Input
frequency
50/60
Hz
+/-4
Hz
(auto
sensing)
50/60
Hz
+/-4
Hz
(auto
sensing)
Rated
power
output
2880
VA
3000
VA
Output
power
capacity
in
watts
2700
W
2700
W
Circuit
breakers
Three
supplemental
circuit
breakers
rated
at
15
amps,
one
for
each
load
segment
Three
supplemental
circuit
breakers
rated
at
15
amps,
one
for
each
load
segment
Fixed
power
cord
Length:
12
ft;
Nema
L5-30P
connection
to
source
Input
connection
type
IEC-320
C20,
connection
to
source
using
country
specific
line
cords
Power
outlets
One
L5-30R
outlet
Six
5-15R
outlets
Six
IEC
C13
outlets
One
IEC
C19
outlet
Audible
noise
at
1
meter
<45
dBA
normal
<50
dBA
Battery
mode
<45
dBA
normal
<50
dBA
Battery
mode
Online
thermal
dissipation
171
Btu
per
hour
171
Btu
per
hour
Chapter
1.
Introduction
3
Summary of Contents for UPS3000 HV
Page 1: ...UPS3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Page 2: ......
Page 3: ...UPS3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Page 28: ...16 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Page 36: ...24 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Page 46: ...34 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Page 54: ...42 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Page 80: ...68 UPS 3000 LV and UPS3000 HV Installation and Maintenance Guide ...
Page 83: ......
Page 84: ... Part Number 40K9691 Printed in USA 1P P N 40K9691 ...