background image

VI.  START UP UPS / MENGHIDUPKAN UPS               

 

1.

 

Make  sure Main  Switch on  the “off” position 
and no load is connected to the outlet. 

2.

 

Connect inlet with power cord to a power 
receptacle with earth ground 

3.

 

Turn  on  the UPS  by  pressing  power button. 
The red led of BATTERY LOW lights for about 2 
seconds and will go out when the battery is in 
good condition

.  

At the same time the green led of  

LINE ON light (if line voltage > 175V and < 
250V) which indicates UPS output is from line 
power. 

4.

 

Disconnect  inlet  from  line  power, the green led 
of  LINE ON will go out while the yellow led of 
INVERTER will light on and audible alarm will 
sound every 4 seconds. 

5.

 

Connect inlet to line power again and then after 
about 2 seconds the yellow led of INVERTER 
will go out while the green led of line on will 
light on. 

6.

 

Now  your  UPS is  ready  for  operation. Connect 
the equipment that is going to be supplied by the 
UPS into the UPS. 

 

 

1.

 

Pastikan  tombol pada posisi “off” dan tidak ada 
beban   yang terpasang pada stopkontak keluaran. 

2.

 

Hubungkan  steker  kabel  daya  ke stopkontak 
jala-jala yang   mempunyai arde.          

3.

 

Hidupkan UPS dengan menekan tombol daya. Led 
merah TEGANGAN BATERAI RENDAH akan 
menyala sekitar 2 detik dan padam kembali bila 
kondisi baterai baik. Bersamaan dengan itu led 
hijau LISTRIK JALA-JALA menyala (bila 
tegangannya > 175V dan < 250V) yang 
menunjukkan keluaran UPS berasal dari listrik 
jala-jala. 

4.

 

Cabut steker kabel daya dari stopkontak jala-jala 
maka led hijau LISTRIK JALA-JALA  padam 
sedangkan led kuning INVERTER akan menyala 
dan buzzer akan berbunyi setiap 4 detik. 

5.

 

Pasang kembali steker maka sekitar 2 detik 
kemudian led kuning INVERTER padam 
sedangkan led hijau akan menyala. 

6.

 

Sekarang  UPS  siap  menjalankan    fungsinya. 
Hubungkan peralatan yang akan diberi pasokan 
daya  pada stopkontak  keluaran  UPS

 

 
 
 

VII.  TABLE OF STATUS INDICATOR  /  TABEL STATUS INDIKATOR 

 

 

Remark : 
 

L1 :  Green Led (Line On)  

NTPL  :  Audible alarm sound every 4 seconds. 

 

L2 :  Yellow Led (Inverter) 

NTPC  :  Audible alarm sound every 1 second. 

 

L3 :  Red Led (Battery Low) 

 

BUZZER LED 

STATUS 

CONDITION 

MAIN  

SWITCH 

NTPL  NTPC  L1 L2 L3 

RECOMMENDED 

SOLUTION 

Normal 

0  1 0 0 

No 

line 

voltage 

0  0 1 0 

Line voltage too low 

Check the line power, make sure 
between 175 -250 Vac. 

Line voltage too high 

0  Check the line power, < 250 Vac. 

Inverter is on at low 
battery voltage 

1  0 1 1 

Save your work now, the inverter 
will be cut off. 

1. Line power is 
normal. 
2. Low battery. 

0  1 0 1 

Summary of Contents for ce 1200

Page 1: ...ICA ...

Page 2: ...UPS to Computer is power fail and battery low UPS Uninterruptible Power Supplies dapat melindungi peralatan Anda yang rentan terhadap gangguan kelistrikan seperti komputer instrument terkomputerisasi PABX faksimili cash register dan peralatan elektronik lainnya UPS ini terdiri atas inverter baterai pengisi baterai rangkaian pengendali stabilisator saklar pengalih dan indikator Saat listrik jala ja...

Page 3: ...UT Internal Battery 1x12V 7AH 2x12V 7AH 3x12V 7AH Sealed lead acid battery Wave Form Synthesized Sinewave Step wave PWM Voltage V 220 5 Frequency Hz 50 INVERTER OUTPUT Efficiency 80 Type V Constant Voltage Voltage A 13 6 27 2 40 8 C H G Current 1 5 Transfer Time ms 4 Maximum Back Up Time min 10 Nominal Load Indicator Led Buzzer Refer to Table of Status Indicator Operation Temperature C 0 40 Dimens...

Page 4: ...UPS Untuk menghidupkan dan mematikan UPS 2 Green Led Led Hijau Indicate output UPS from line power Menunjukkan keluaran UPS dari listrik jala jala 3 Yellow Led Led Kuning Indicate output UPS from inverter Menunjukkan keluaran UPS dari inverter 4 Red Led Led Merah Indicate battery low Menunjukkan keadaan battery hampir habis 5 RS232 Connector Konektor RS232 For communication between UPS and compute...

Page 5: ... jalankan RUPS 2000 mulai dari menu RUPS 2000 RUPS Manager Untuk setting yang lain lihat pada petunjuk pemakaian dalam CD RUPS 2000 V OPERATION PROCEDURE CARA MENGOPERASIKAN 1 Turn on procedure a Press on main switch at the front panel b Turn on the load connected to the outlet 2 When the line power is interrupted In case of line power is interrupted off or voltage is too low high inverter convert...

Page 6: ...daya Led merah TEGANGAN BATERAI RENDAH akan menyala sekitar 2 detik dan padam kembali bila kondisi baterai baik Bersamaan dengan itu led hijau LISTRIK JALA JALA menyala bila tegangannya 175V dan 250V yang menunjukkan keluaran UPS berasal dari listrik jala jala 4 Cabut steker kabel daya dari stopkontak jala jala maka led hijau LISTRIK JALA JALA padam sedangkan led kuning INVERTER akan menyala dan b...

Page 7: ...low 1 Check battery voltage 2 Charger battery 10 hour by kept the main switch in on position when AC mains normal 3 Call for service When AC main failure and inverter does not work Problem in inverter circuit Call for service Communication from UPS to computer fail 1 Interface cable not connected 2 Software has not been installed or configure properly 3 Interface cable or monitor card is broken 1 ...