ICAR PQS
rev8 may18
48 / 86
COMMANDS menu
It performs one of the operations in the “COMMANDS”menu
(Cx=1…18)
23
OUTPUT FUNCTION TABLE
The following table shows all the functions that can be attributed to the OUTn programmable digital inputs.
Each output can be configured so it has a normal or reverse (NOR or REV) function.
Some functions require another numeric parameter, defined in the index (x) specified by parameter P04.n.02.
See menu
M04 Master outputs
and
M06…M13 Slave outputs
for more details.
FUNCTION
DESCRIPTION
OFF
Output always de-energized
ON
Output always energized
Step x
Capacitor step nr.x
Global alarm 1
Energised when global alarm 1 is active
Global alarm 2
Energised when global alarm 2 is active
Global alarm 3
Energised when global alarm 3 is active
Fan
Panel ventilation fan
Manual mode
Active when the regulator is in MAN mode
Automatic mode
Active when the regulator is in AUT mode
Limit threshold LIM x
Output driven by LIM limits
Pulse PULx
Output driven by PUL pulses
Remote variable REM x
Output is remote controller by REM variable
Alarms A01-Axx
When the selected Axx alarmi s present, the output ias activated (x=1… alarm number)
Alarms UA1..UAx
When the selected UAx user alarm is present, the output is activated (x=1… 8)
24
MEASURE TABLE FOR LIMITS / ANALOG OUTPUTS
The following table lists all measures that can be associated with the limits (menu M20) and outputs (menu M23).
The codes selected in the parameters P20.n.01 and P23.n.02 correspond to the measures below.
To facilitate comparison with the three-phase measures, some 'virtual' measures are provided, that contain the highest
measurements across the three phases. These measures are identified by the presence of the word MAX in the measure code.
Example: If you want to apply a maximum limit of 10% on the content of 5.harmonics in the current of the system, when you have
a three-phase current, set LIM1 with H. I MAX, with channel no. set to 5. The device will consider the highest of the harmonic
content of the 5.o order among the three currents I L1, I L2 and I L3.
Settings:
P20.1.01 = H. I MAX (highest current harmonic among 3 phases)
P20.1.02 = 5 (5.th harmonic)
P20.1.03 = max (compare with max threshold)
P.20.1.04 = 10 (threshold = 10%)
Nr
Measure code
Description
00
OFF
Measure disabled
01
V L1-N
Phase voltage L1-N
02
V L2-N
Phase voltage L2-N
03
V L3-N
Phase voltage L3-N
04
I L1
Phase current L1
05
I L2
Phase current L2
06
I L3
Phase current L3
07
V L1-L2
Phase-to-phase voltage L1-L2
08
V L2-L3
Phase-to-phase voltage L2-L3
09
V L3-L1
Phase-to-phase voltage L3-L1
10
W L1
Active power L1
11
W L2
Active power L2
12
W L3
Active power L3
13
var L1
Reactive power L1
14
var L2
Reactive power L2
15
var L3
Reactive power L3
16
VA L1
Apparent power L1
17
VA L2
Apparent power L2
18
VA L3
Apparent power L3
19
Hz
Frequency
20
Cosphi L1
Cosphi L1
21
Senphi L1
Senphi L1
22
Cosphi L2
Cosphi L2
23
Senphi L2
Senphi L2
24
Cosphi L3
Cosphi L3
25
Senphi L3
Senphi L3