58
14.2
Secondary Networks
14.2.1
Modbus RTU
•
The gateway acts as a Modbus RTU master via the secondary RS-485
port. Supported Modbus functions are indicated in Table 9.
Table 9: Supported Modbus Master Functions
Function Code
Function
3
Read multiple registers
16
Write multiple registers
•
The slave response timeout is fixed at 3s.
•
Network characteristics selections
o
Baud rate: 2400 / 4800 / 9600 / 19200 / 38400 bps
o
Parity: odd / even / none (1 stop bit) / none (2 stop bits)
•
Console holding register number entry radix is decimal (e.g. 10 = 10
10
)