60
14.2.3
Sullair Supervisor Protocol
•
The gateway acts as a Sullair Supervisor Protocol network monitor via the
secondary RS-485 port. It can automatically adapt to the Supervisor
network configuration (sequencing or non-sequencing/slave mode).
•
Any numerically-addressed parameter defined by the Supervisor protocol
is directly accessible (machine type = parameter #1, etc.). However,
some Supervisor data objects are not natively numerically-addressed. For
these data objects, the additional parameter numbers indicated in Table
10 have been assigned.
Table 10: Additional Supervisor Parameter Assignments
Parameter
Number
Item Note
Source
100 Capacity
101 P2
102 Run
hours
103 Run
status
0 = E-stop
1 = remote stop
2 = manual stop
3 = standby
4 = starting
5 = load
6 = unload
7 = trim
8 = full load
104 Mode
0 = auto
1 = continuous
N
e
t / quick status
105 P1
106 P2
107 P3
108 P4
109 T1
110 T2
111 T3
112 T4
113 T5
114 T6
115 Run
time
116 Load
time
117 Digital
outputs
118 Digital
inputs
Info status
122 Online
0 = offline (not sequencing)
1 = online (sequencing)
123 Faulted
0 = not faulted
1 = faulted
Net /
quick
status
Summary of Contents for DNET-100
Page 8: ...7 2 Mechanical Diagrams 2 1 Enclosure Figure 2 Enclosure Dimensions units are inches ...
Page 9: ...8 2 2 Mounting Clip Figure 3 Mounting Clip Dimensions units are inches ...
Page 11: ...10 ASD Link LEDs Reserved LEDs ASD 2 ASD 3 ASD 1 Figure 6 Top View ...
Page 39: ...38 Figure 15 HyperTerminal Configuration Screen 3 ...
Page 68: ...67 16 Notes ...
Page 69: ...68 ...