121
ICC
•
Click
Create
.
Repeat these steps for the other two AO objects, increasing the
Object Name
by 1,
Instance
by 1, and
Database
Addr
by 4 each
time.
o
Create input objects for floor 1’s command data
For the first object, enter the following:
•
Select
Analog Input
from the
Type
selection group.
•
Enter “F1 Cmd Data 1” into the
Object Name
field.
•
Enter “1” into the
Instance
field.
•
Enter “100” into the
Database Addr
field.
•
Select
32-bit Unsigned
from the
Data Type
dropdown
menu.
•
Enter “1” into the
Multiplier
field.
•
Click
Create
.
Repeat these steps for the other two AI objects, increasing the
Object Name
by 1,
Instance
by 1, and
Database
Addr
by 4 each
time.
o
Create output objects for floor 2’s monitor data
For the first object, enter the following:
•
Select
Analog Output
from the
Type
selection group.
•
Enter “F2 Mon Data 1” into the
Object Name
field.
•
Enter “4” into the
Instance
field.
•
Enter “12” into the
Database Addr
field.
•
Select
32-bit Unsigned
from the
Data Type
dropdown
menu.
•
Enter “1” into the
Multiplier
field.
•
Click
Create
.
Repeat these steps for the other two AO objects, increasing the
Object Name
by 1,
Instance
by 1, and
Database
Addr
by 4 each
time.
o
Create input objects for floor 2’s command data
For the first object, enter the following:
•
Select
Analog Input
from the
Type
selection group.
•
Enter “F2 Cmd Data 1” into the
Object Name
field.
•
Enter “4” into the
Instance
field.
•
Enter “112” into the
Database Addr
field.
•
Select
32-bit Unsigned
from the
Data Type
dropdown
menu.
•
Enter “1” into the
Multiplier
field.
•
Click
Create
.
Repeat these steps for the other two AI objects, increasing the
Object Name
by 1,
Instance
by 1, and
Database
Addr
by 4 each
time.