245
ICC
value(s) (if the write function is enabled). For more information on configuring
MELSEC service objects, refer to section 8.7.9.2.
11.10.2.2
MELSEC Device Codes
For user convenience, the gateway provides internal support for a certain number
of device codes (refer to Table 7). However, this in no way limits the variety of
device codes that the gateway can target. The user has the ability to specify any
device code that is supported by the targeted MELSEC server equipment (refer
to sections 8.7.9.2 and 11.7.3.3.5). Note that device codes are not case-
sensitive (i.e. “C3” is interpreted the same as “c3”).
Table 7: MELSEC Device Code List
Device
Type
3E Frame
Device Code
1E Frame
Device Code
Annunciator (F)
Bit
93
H
N/A
Counter Coil (CC)
Bit
C3
H
4343
H
Counter Contact (CS)
Bit
C4
H
4353
H
Counter Current Value (CN)
Word
C5
H
434E
H
Data Register (D)
Word
A8
H
4420
H
Direct Input (DX)
Bit
A2
H
N/A
Direct Output (DY)
Bit
A3
H
N/A
Edge Relay (V)
Bit
94
H
N/A
Index Register (Z)
Word
CC
H
N/A
Input (X)
Bit
9C
H
5820
H
Internal Relay (M)
Bit
90
H
4D20
H
Latch Relay (L)
Bit
92
H
N/A
Link Register (W)
Word
B4
H
5720
H
Link Relay (B)
Bit
A0
H
4220
H
Link Special Register (SW)
Word
B5
H
N/A
Link Special Relay (SB)
Bit
A1
H
N/A
Motion Register (#)
Word
E0
H
N/A
Output (Y)
Bit
9D
H
5920
H
Retentive Timer Coil (SC)
Bit
C6
H
N/A
Retentive Timer Contact (SS)
Bit
C7
H
N/A
Retentive Timer Current Value (SN)
Word
C8
H
N/A
Special Register (SD)
Word
A9
H
N/A
Special Relay (SM)
Bit
91
H
N/A
Step Relay (S)
Bit
98
H
N/A
Timer Coil (TC)
Bit
C0
H
5443
H
Timer Contact (TS)
Bit
C1
H
5453
H
Timer Current Value (TN)
Word
C2
H
544E
H