96
ICC
8.8.5
TCS Basys Master
TCS Basys Master can be configured on the RS-485 port by selecting
Basys
Master
from the protocol dropdown menu. The TCS Basys Master protocol uses
service objects to make requests. For more information on service objects, refer
to section 8.5. Each position in a service object is mapped to 2 bytes in the
database (the data size is fixed at 16-bit, as this is the native data size of TCS
Basys data). For more information on TCS Basys service objects, refer to
section 11.4.2.
8.8.5.1
Protocol Selection Group
Protocol
Select
Basys Master
from this dropdown menu.
Baud Rate
Select the desired network baud rate from this dropdown menu.
Timeout
This is the time in milliseconds that the device will wait for a response from a
drive after sending a request.
Scan Rate
This is the time the device will wait between sending requests. This may be
useful if drives require additional time between requests. If no additional delay
time is needed, set this field to 0. For more information, refer to section 8.4.
8.8.5.2
TCS Basys Service Object Configuration
This section describes the configurable fields for a TCS Basys service object. For
more information on TCS Basys service object editing options, refer to section
8.6.
Description
This field is a description of the service object. It is not used on the gateway, but
serves as a reference for the user. Enter a string of up to 16 characters in length.
Dest Address
This field indicates the destination address of the target device on the network
that will be accessed by this service object. Enter a value between 0 and 255.
Start Position
This field defines the starting position number for a given function code. Enter a