background image

ICC

 

INDUSTRIAL CONTROL COMMUNICATIONS, INC. 

Page 5 of 10 

05.23.2014 

 

 

0720-160-MC 

 

1600 Aspen Commons, Suite 210 
Middleton, WI, USA    53562 
Tel:  (608) 831-1255 
Fax:  (608) 831-2045 
Email: sales@iccdesigns.com 

BACnet 

Object

 

Mapping

 

Table 2 provides a listing of the BACnet objects supported by the configuration preloaded on the ETH-1000 
gateway. 

Table 2:  BACnet Object Mapping 

Instance ID  Object Name 

Description 

Units 

Multiplier  Definition Of Encoded Data 

AI0 

S1 Module State 

Fault & Module State for 

Sensor 1 

No Units 

(95) 

1.000000 

0  – Warm Up 
Bit 0 – Normal 
Bit 1 – Cal/Setup 
Bit 2 – Factory 
Bit 3 – Trouble 
Bit 8 – Cal Sum 
Bit 9 – Under Range 
Bit 10 – Flow Loss 
Bit 11 – Under Voltage 
Bit 12 – Temperature 
Bit 13 – Prog Cksum 
Bit 14 – Lamp Fail 

AI1 

S1 Gas Number 

Gas Number for Sensor 1 

No Units 

(95) 

1.000000 

0 to 44 (Refer to manual for 
definition) 

AI2 

S1 Concentration 

Gas Concentration for 

Sensor 1 

PPM (96)  1.000000 -20 to 1050 

AI3 

S1 Alarm State 

Alarm State for Sensor 1 

No Units 

(95) 

1.000000 

0 - None 
Bit 0 – Caution 
Bit 1 – Warning 
Bit 2 – Alarm 

AI4 

S1 Caution Level 

Caution Setpoint for Sensor 

PPM (96)  1.000000 30 to 980 

AI5 

S1 Warning Level 

Warning Setpoint for Sensor 

PPM (96)  1.000000 40 to 990 

AI6 

S1 Alarm Level  Alarm Setpoint for Sensor 1  PPM (96)  1.000000 50 to 1000 

AI10 

S2 Module State 

Fault & Module State for 

Sensor 2 

No Units 

(95) 

1.000000 

0  – Warm Up 
Bit 0 – Normal 
Bit 1 – Cal/Setup 
Bit 2 – Factory 
Bit 3 – Trouble 
Bit 8 – Cal Sum 
Bit 9 – Under Range 
Bit 10 – Flow Loss 
Bit 11 – Under Voltage 
Bit 12 – Temperature 
Bit 13 – Prog Cksum 
Bit 14 – Lamp Fail 

AI11 

S2 Gas Number 

Gas Number for Sensor 2 

No Units 

(95) 

1.000000 

0 to 44 (Refer to manual for 
definition) 

AI12 

S2 Concentration 

Gas Concentration for 

Sensor 2 

PPM (96)  1.000000 -20 to 1050 

AI13 

S2 Alarm State 

Alarm State for Sensor 2 

No Units 

(95) 

1.000000 

0 - None 
Bit 0 – Caution 
Bit 1 – Warning 
Bit 2 – Alarm 

Summary of Contents for ETH-1000

Page 1: ...to connect a preconfigured ETH 1000 gateway to a MSA Chillgard LC Refrigerant Monitor This document also contains the BACnet object mapping for the application and some troubleshooting tips For more i...

Page 2: ...and G on the Chillgard LC to the gateway s terminal block at terminals TB 2 B TB 1 A and TB 6 GND as shown in Figure 2 This terminal block on the Chillgard LC will have wires for both the gateway and...

Page 3: ...n studio html Ethernet Network Settings The network settings may need to be modified to be compatible with your network These settings can be modified in the ICC Configuration Studio by selecting Ethe...

Page 4: ...160 MC 1600 Aspen Commons Suite 210 Middleton WI USA 53562 Tel 608 831 1255 Fax 608 831 2045 Email sales iccdesigns com Figure 5 BACnet Device Settings Table 1 Default BACnet Settings Setting Default...

Page 5: ...definition AI2 S1 Concentration Gas Concentration for Sensor 1 PPM 96 1 000000 20 to 1050 AI3 S1 Alarm State Alarm State for Sensor 1 No Units 95 1 000000 0 None Bit 0 Caution Bit 1 Warning Bit 2 Ala...

Page 6: ...ion AI22 S3 Concentration Gas Concentration for Sensor 3 PPM 96 1 000000 20 to 1050 AI23 S3 Alarm State Alarm State for Sensor 3 No Units 95 1 000000 0 None Bit 0 Caution Bit 1 Warning Bit 2 Alarm AI2...

Page 7: ...1 S5 Gas Number Gas Number for Sensor 5 No Units 95 1 000000 0 to 44 Refer to manual for definition AI42 S5 Concentration Gas Concentration for Sensor 5 PPM 96 1 000000 20 to 1050 AI43 S5 Alarm State...

Page 8: ...Bit 10 Flow Loss Bit 11 Under Voltage Bit 12 Temperature Bit 13 Prog Cksum Bit 14 Lamp Fail AI61 S7 Gas Number Gas Number for Sensor 7 No Units 95 1 000000 0 to 44 Refer to manual for definition AI62...

Page 9: ...1 Alarm Sample 1 Alarm State On Off BI11 S2 Caution Sample 2 Caution State On Off BI12 S2 Warning Sample 2 Warning State On Off BI13 S2 Alarm Sample 2 Alarm State On Off BI21 S3 Caution Sample 3 Cauti...

Page 10: ...hould light green when the gateway is powered and should flash green when the gateway is connected via USB i If this is not observed check the gateway s power b The RS 485 RX LED should flash red The...

Reviews: