197
ICC
11.3
BACnet
The gateway supports both BACnet/IP client and server (via Ethernet), BBMD,
and both BACnet MS/TP client and server drivers (via RS-485). Both MS/TP
client and server drivers act as masters on the network, meaning they are
actively involved in token management.
11.3.1
Protocol Implementation Conformance Statement
BACnet Protocol
Date:
September 30, 2011
Vendor Name:
ICC, Inc.
Product Name:
Millennium Series Ethernet Gateway
Product Model Number:
ETH-1000
Applications Software Version: V2.300
Firmware Revision:
V2.300
BACnet Protocol Revision:
2
Product Description:
The ETH-1000 is an Ethernet to RS-485 multiprotocol gateway. This
product supports native BACnet, connecting directly to the IP and/or
MS/TP LAN using baud rates of 4800, 9600, 19200, 38400, 57600,
76800, and 115200. The device can be configured as a BACnet/IP client
and/or BACnet/IP server, BBMD, and MS/TP client and/or MS/TP
server.
BACnet Standard Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing – ReadProperty-A (DS-RP-A)
Data Sharing – ReadProperty-B (DS-RP-B)
Data Sharing – ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing – WriteProperty-A (DS-WP-A)
Data Sharing – WriteProperty-B (DS-WP-B)
Data Sharing – WritePropertyMultiple-B (DS-WPM-B)
Data Sharing – COV-B (DS-COV-B) (BACnet/IP only)
Device Management – Dynamic Device Binding-A (DM-DDB-A)
Device Management – Dynamic Device Binding-B (DM-DDB-B)
Device Management – Dynamic Object Binding-B (DM-DOB-B)
Device Management – DeviceCommunicationControl-B (DM-DCC-B)
Device Management – ReinitializeDevice-B (DM-RD-B)