RS-485 Protocol Configuration
The following section describes how to configure the RS-485 protocols on the
gateway with the configuration utility. For more details on how to use the
configuration utility, refer to the
ICC Gateway Configuration Utility User’s Manual
.
8.8.1
A.O. Smith AIN Slave
A.O. Smith AIN (Advanced Internal Network) Slave can be configured on the RS-
485 port by selecting
AO Smith AIN Slave
from the protocol dropdown menu.
The AIN Slave protocol uses service objects to define desired parameters from
the master to capture the values for and to write to. For more information on
service objects, refer to section 8.5. Each parameter in a service object is
mapped to 2 bytes in the database (the data size is fixed at 16-bit, as this is the
native data size of AIN parameters). For more information on parameter
mapping, refer to section 11.1.2.
8.8.1.1
Protocol Selection Group
Protocol
Select
AO Smith AIN Slave
from this dropdown menu.
Baud Rate
Select the desired network baud rate from this dropdown menu.
8.8.1.2
AIN Service Object Configuration
This section describes the configurable fields for an AIN service object. For more
information on AIN service object editing options, refer to section 8.6.
Description
This field is a description of the service object. It is not used on the gateway, but
serves as a reference for the user. Enter a string of up to 16 characters in length.
Block Num
This field indicates the block number that the desired parameters are located in.
Enter a value between 0 and 29 to target a specific block.
Start Param
This field defines the starting parameter number for a range of parameters
associated with this service object. Enter a value between 0 and 255.
Num Params
This field defines the number of parameters associated with this service object.
Enter a value between 1 and 255.