67
16.7.1
Command Parameters
Parameter
Bit Function Bank
Mask Adjustment Range
Multiplier
0001 word
Frequency
command 0 FFFF
0.00
∼
400.00Hz
Actual frequency will be limited by
LL, UL and Fmax.
0.01
0002 0
RUN
command
0
⎯
0: Stop
1: Run
⎯
1
Reserved
⎯
2
Forward
•
reverse
run selection
0:
reverse
1: forward
3
Acc/dec #1 / #2
selection
0: Acc / dec #1
1: Acc / dec #2
4
Reserved
⎯
5
Reserved
⎯
6
Reserved
⎯
7
Jog mode selection
0: Normal (acc/dec mode)
1: Jog mode
8
Feedback control
0: Feedback valid
1: Feedback invalid
9
Compulsory
DC
injection braking
mode
0: No compulsory DC injection
braking
1: Compulsory DC injection below
DC INJECTION START
FREQUENCY
A
Fundamental
parameter switching
0: V/F #1
1: V/F #2
B
Gate block command
(coast stop
command)
0:
Normal
1: Gate block
C
Emergency
off
command
0: Does nothing
1: Emergency off
D
Reset
command
(trip clear)
0: Does nothing
1: Reset
E
Reserved
⎯
F
Reserved
⎯
0003
word
RS232 command /
frequency selection
0 0003
0000:
FREQUENCY MODE
SELECTION
,
COMMAND
MODE SELECTION
settings
0001: RS232C commands valid
0002: RS232C frequency valid
0003: RS232C commands and
frequency valid
⎯
0004
word
Preset speed run
command
0
000F
0000: Output frequency selected
by
FREQUENCY MODE
SELECTION
0001
∼
000F: speeds 1
∼
15
⎯