73
16.7.4
Fundamental Parameters #2
Parameter
Function / Title
Bank
Mask
Adjustment Range
Multiplier
0034
BASE FREQUENCY #2
0 / 1
FFFF
09C4
∼
9C40 (25.00
∼
400.00)
0.01
0035
MAXIMUM OUTPUT
VOLTAGE #2
0 / 1
FFFF
0000
∼
0258 (0
∼
600)
1
0036
VOLTAGE BOOST #2
0 / 1
FFFF
0000
∼
012C (0.0
∼
30.0)
0.1
0037
ELECTRONIC THERMAL
PROTECT LVL #2
0 / 1
00FF
000A
∼
0064 (10
∼
100)
1
0038
STALL PROTECTION
SELECTION #2
0 / 1
0040
0000: ON
(0)
0040: OFF
(1)
⎯
0039
0
STALL PROTECTION
LEVEL #2
0 / 1
00FF
000A
∼
00D7 (10
∼
215)
1
003A
ACCELERATION TIME #2
0 / 1
FFFF
0001
∼
EA60 (0.1~ 6000.0)
0001
∼
EA60 (0.01~ 600.00)
0.1
0.01
003B
DECELERATION TIME #2
0 / 1
FFFF
0001
∼
EA60 (0.1~ 6000.0)
0001
∼
EA60 (0.01~ 600.00)
0.1
0.01
003C
ACC/DEC PATTERN #2
SELECTION
0 / 1
0030
0000: Linear
(0)
0010: Self-adjusting
(1)
0020: S-Pattern #1
(2)
0030: S-Pattern #2
(3)
⎯
003D
ACC/DEC #1/#2 SWITCH
FREQUENCY
0 / 1
FFFF
0000
∼
Fmax
0.01
16.7.5
Panel Control Parameters
Parameter
Function / Title
Bank
Mask
Adjustment Range
Multiplier
003E
DIRECTION SELECTION
(FORWARD/REV)
0 / 1
0004
0000: Reverse
(0)
0004: Forward
(1)
⎯
003F
STOP PATTERN
SELECTION
0 / 1
0040
0000: Decelerated stop
(0)
0040: Coast stop
(1)
⎯
0040
FUNDAMENTAL PARAM
SWITCHING
0 / 1
0004
0000: V/F #1
(1)
0004: V/F #2
(2)
⎯
0041
ACCEL/DECEL #1/#2
SELECTION
0 / 1
0008
0000: Accel / decel #1
(1)
0008: Accel / decel #2
(2)
⎯
0042
PANEL RESET
SELECTION
0 / 1
0030
0000: All possible
(0)
0010: OL only
(1)
0020: OL, OC only
(2)
⎯
0043
PANEL FEEDBACK
CONTROL
0 / 1
0001
0000: Feedback valid
(0)
0001: Feedback invalid
(1)
⎯
Summary of Contents for ETH-200