background image

Model VIP+

 

Owner's Manual 

Operation and Maintenance 

KEEP YOUR VENT CLEAN. Your vent system should be examined annually by a qualified service company for the presence of soot or debris. Any 
accumulation should be removed. Also, the vent system should be inspected periodically for the following: 
 
1.

 

Any leakage of condensate or combustion by-product at joints should be removed. 

2.

 

A defective drain trap loop should be repaired to prevent any leakage of exhaust gases inside the building area. 

3.

 

Any sign of corrosion. 

General Installation Notes 

1.

 

Model VIP+ is to be installed in accordance with these installation instructions and with those of the appliance manufacturer. 

2.

 

Installation is to be in accordance with local building code requirements and National Codes. 

3.

 

Size the vent in accordance with the appliance manufacturer’s instructions. ICC will calculate correct vent sizing on request. 

4.

 

Make sure you read the appliance installation instructions for vent limitations such as maximum horizontal length, maximum number of elbows, 
total vent height, common venting option, and other limitations that may affect the design and installation of this vent. 

5.

 

The maximum height of un-guyed vent above the roof is 6 feet. 

6.

 

The vent shall extend at least 3ft. above its point of penetration with the roof and at least 2 ft. higher than any wall, roof or adjacent building 
within 10 ft of it. 

7.

 

DO NOT FILL THE AIR SPACE

 around the vent with insulation or any other material.  

8.

 

Do  not  allow  sawdust  or  construction  debris

  to  accumulate  around  the  vent.  Clean  all  areas  surrounding  the  vent  before  closing  up  any 

enclosed areas. 

Planning your Installation 

P

rior to starting your installation, we suggest you take the following into consideration: 

 
1.   Check the appliance manufacturer's installation instructions to see all possible vent configurations. 
2.  Review  all  your  options  for  the  appliance  location  and  also  venting  configuration.  Try  to  minimize  the  alteration  and  reframing  of  structural 

components of the building (wall studs, water pipes, electrical wiring, ceiling joists, roof rafters, etc.). It may be easier to change the location of 
your appliance than to modify the building structure. 

3. 

Use only Model VIP+ listed components

. Do not use damaged parts. 

4.  Any penetrations of roof, ceilings, or floors must be properly fire-stopped as per venting applications described in these installation instructions. 
5.  Contact your local building authority and/or fire officials for permits, restrictions and installation inspections. You may also wish to contact your 

building insurance representative. 

Tool checklist  

Tools and equipment you may need for your installation. 

 

- Eye protection 

 

- Gloves 
- Tape Measure 

 

- Extension cord 
- Marking pencil 

 

- Nails 

- Stud sensor 
- Square 
- Circular saw 
- Hand saw 
- Drill 

 

- Drill bits 

- Keyhole saw 
- Ladder 
- Level 
- Pliers 
- Caulking gun 
- Proper application sealant 

- Hammer 
- Screwdrivers 

 

- Screws 
- Plumb Bob 
- Cold chisel 
 

Rules of Safety  

1.  Wear gloves when handling metal parts with sharp edges. 
2.  Wear safety glasses. 
3.  Electrical tools must be grounded. 
4.  If a ladder, scaffold or a scissor lift platform is required, it must be in good condition, installed on a firm surface, and leveled. 
5.  When cutting a wall, floor or ceiling, be careful not to damage wiring, gas or water pipes. If these elements need to be relocated, work should be 

done by a qualified person.  

Summary of Contents for VIP+ Air Insulated

Page 1: ...he ICC Model VIP venting system until you have carefully read the appliance and vent system installation instructions Use only ICC Model VIP components Failure to do so will void the certification and...

Page 2: ...0 Base Support 10 Wall Support 11 Wall Guide 12 Floor Guide 12 Support Methods and System Design Limits 13 Rigid Structural Brace Specifications 14 Elbows and Offsets 14 Guy Wire 15 Roof and Floor Pen...

Page 3: ...id oil or solid fuel fired appliances Also complies with operation less than one hour at temperatures not exceeding 760 C 1400 F and brief operation maximum 10 minutes at temperatures not exceeding 92...

Page 4: ...6 to 24 6 7 Ventilated Firestop See Roof and Floor Penetrations section for details Part Numbers The following section describes how part number are defined for most of the major VIP products Please r...

Page 5: ...for flue and casing 26 ga min up to 16 and 24 ga min 18 and over C Galvalume Alu Zinc Available for casing only 26 ga min up to 16 and 24 ga min 18 and over Standard materials only for other options...

Page 6: ...ing the vent before closing up any enclosed areas Planning your Installation Prior to starting your installation we suggest you take the following into consideration 1 Check the appliance manufacturer...

Page 7: ...amix TC 2280 F 1250 C Outer Joints Any Silicone Sealant with a min rating of 400 F 400 F Outer Joints Any Silicone Sealant with a min rating of 400 F 400 F Fortafix Ceramix TC cure time Air dry for 24...

Page 8: ...to chimney label for flue gases direction Step 3 Assemble the flue locking band and secure by tightening the bolt Do not remove the excess of sealant Step 4 Install locking band insulation strip arou...

Page 9: ...nd Bead of Fortafix Ceramix TC just above the formed bead when chimneys are joined together before interior locking band assembly Step 4 Assemble the interior locking band around the flue and secure b...

Page 10: ...7 effective length that is welded to a steel plate The chimney section has female and male ends forming just like any standard length It can be connected to any other piece of piping with proper locki...

Page 11: ...bands and sealant see Chimney Joint Connection Section for specific instructions It is supplied with both an Interior Locking Band a special External Finishing Band top female side and an Insulation S...

Page 12: ...with a minimum of 3 anchors on each side by others See Table 7 for Maximum Vertical Spacing between 2 Supports or Guides MVS Figure 12 Figure 13 Floor Guide The Floor Guide is mainly used as a chimney...

Page 13: ...plication Table 6 Maximum Supported Chimney Height and Support Method MCH Support Method VIP Chimney Model MCH feet VIP AIR Insulated VIP 1 Fiber VIP 2 Fiber VIP 4 Fiber Base Support 6 to 24 51 39 30...

Page 14: ...burning appliances Chimneys for combination fuel heating appliances that are capable of burning solid fuel or are convertible to solid fuel are limited to 30 slope even if the current choice of fuel i...

Page 15: ...The Guy Wire Band is made to hook up 3 guy wire by others at 120 apart or to be secured with Rigid Roof Brace by others The cables are secured to the roof by mean of tensioners by others and anchors b...

Page 16: ...ss than one hour at temperatures not exceeding 760 C 1400 F and brief operation maximum 10 minutes at temperatures not exceeding 906 C 1700 F An Insulated Radiation Shield must be used where a chimney...

Page 17: ...of combustible material It is designed to be installed on a flat roof or roof curb 8 to 16 high The roof framing dimensions are presented in Table 8 in the previous Section 1 The Radiation Shield is i...

Page 18: ...primarily used for Engines or High Temperature Applications where a chimney section passes through a roof made of combustible material It is designed to be installed on a flat roof or roof curb 4 to 1...

Page 19: ...to 6 inches water column can effectively use the Expansion Length Table 9 Allowable lengths for 1 4 thermal expansion T Gas T Surroundings T F Length between fixed points 200 12 6 300 8 4 400 6 3 500...

Page 20: ...oint Connection Section 4 Bellow Joint is used for axial movements and vibration only and must be accurately supported and guided This part has limited lateral movement Lateral offsets and parallel mi...

Page 21: ...asket between the two flanges and secure with the supplied bolts Use a star tightening pattern of the bolts for better stability Re tighten the compression band bolt if necessary 6 Install Insulation...

Page 22: ...all precautions for cleaning sealed surfaces and use proper sealant as described in the Sealant Application Chart section see Table 4 It can be used in horizontal or vertical runs and also between el...

Page 23: ...Model VIP 23 Owner s Manual Figure 36...

Page 24: ...Model VIP 24 Owner s Manual Figure 37...

Page 25: ...ending from the penetration through any concealed spaces to or through the roof so as to maintain the integrity of the fire separations required by the applicable building code The enclosure shall be...

Page 26: ...be used to integrate automatic cleaning or fire suppression devices by others to a Grease Duct installation The Nozzle Length comes with a 3 4 NPT nipple both ends that can be connected to an automat...

Page 27: ...sote makes an extremely hot fire For this reason the duct should be inspected at least once every two months to determine if a creosote or soot buildup has occurred Consult local code and officials as...

Page 28: ...m position 2 T2 Grease Tee Figure 46 has inverted female and male ends and covers mostly horizontal grease dam configurations Refer to Figure 47 for dam position When ordering you GreaseTee please spe...

Page 29: ...Fan Adapter Roof Curb by others Exhaust Hoods by others Grease Duct Wye Tee Cap Grease Tee T2 P3 Dam Position Chimney Sections 90 Tee Standard TR Horizontal Band Base Support Base Support Supporting...

Page 30: ...vanized or steel surfaces must be protected at all times by a minimum of one base coat of primer and one finish coat of heat resistant and corrosion resistant paint Stainless steel surfaces need not b...

Reviews: