ELEVATION SERIES CIM CUBERS
SEQUENCE OF OPERATIONS
17
CONTROL BOARD - ANTI-SLUSH
During the first 3 cycles as the water temperature reaches 36 degrees F. the Water Pump will shut off for
20 seconds to reduce the possibility of slush developing in the Sump. After the first 3 cycles, Anti‐Slush
will only occur if the Sump water temperature reaches 28 degrees F.
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage
Components
R1
R2
R3
R4
R5
R6