Operation and Adjustment ICEU060
Page 12
The information shown below covers a wide range of air and water temperatures. It is intended as a
guideline only, and is based on data compiled from NEW Clean units. Allow a variation from each end of
the range given.
Refrigeration System Pressures:
Freeze Cycle Time -
20-25 Minutes
High Side (Discharge)
Defrost Cycle Time
–
2-3 Minutes
End of Freeze Cycle 125-130 PSI
Compressor Amps
Harvest Cycle
83-125 PSI
Freeze Cycle – 3.6 to 4.3
Low Side (Suction)
Harvest Cycle – 3.6 to 7.7
End of Freeze Cycle 1-3 PSI
Harvest Cycle (Max) 120 PSI
Adjustment Of The Cube Size
Adjust only when cubes are too large or too small.
(See the illustration at the right)
1.
Remove the front panel, locate knob.
2.
To increase the cube size, turn knob 1/8 turn
clockwise. To decrease the cube size, turn the knob
1/8 turn counter clockwise.
3.
Observe the size of the cubes in the next two harvest
cycles. If more adjustment is needed, continue
adjustments until the correct size is obtained.
Adjustment Of The Bin Thermostat Control
Adjust the bin thermostat when the icemaker turn off too
soon (ice level low) or when it turns off too late (ice storage
bin overfills.)
To increase the ice level in the storage bin:
1.
Rotate the bin thermostat adjustment screw (located
under the front panel on the control box cover)
clockwise 1/8 turn at a time until the ice level that the
machine maintains is correct.
2.
Rotate the bin thermostat adjustment screw
counterclockwise 1/8 turn at a time until the ice level is
correct.