Proper Tube Routing
When installing the discharge and liquid lines from the remote condenser to the icemaker, please use the
following guidelines:
1. The remote condenser (#2) should always be installed above the icemaker (#4) as shown with a
vertical air flow.
2. All excess tubing (#1) should be routed inside the building and coiled in a vertical spiral as shown
(#3), to prevent oil trapping in the lines. Any tubing run outside should be insulated to protect it from
surrounding ambient conditions. Tubing should follow straight line routing whenever possible. The
lowest spot in the tubing run should be the connection at the rear of the icemaker.
Vertical Air flow