IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
____________________________________________________________________________________________
IMU307-1 GB Ind. B
63
Main characteristics
adjustments
operating level 46-INeg>
0.15 to 0.50 In (steps of 0.05 In )
minimum response time tINeg>min
0.5 to 10 s (steps of 0.1s )
operating curve
see figure below
time/current characteristics
t(s) =
)²
In
/
INeg
(
²
CK
with max. time = 50 s
K = adjustment = (In machine/In CT)
C = 8 to 40 s steps of 1s