5.7 Start menu
This menu allows the parameter setting of the too long start, locked rotor, limitation of the
number of start and inhibition of hot start functions: setting in and out of order, adjustment of
the start motor and inhibition of hot start threshold, adjustment of the time delays (start,
locked rotor, restarting), assignment of the output units for the trip (too long start, locked rotor
and inhibition of start).
MAIN MENU
STARTING FCT.
Number of starts, too long start, rotor
stall after start period
SETTING
set 1
Choose the setting group
set 1 or set 2
LONG ST/ST.ROTOR
Active
Choose Active for too long start and
locked rotor (51 LR)
Active or Inactive
START THRESHOLD
2.0 * Iref
Detection Threshold of the start of
the motor (Iref: thermal current of
reference)
1.0 to 10.0 * Iref
START DELAY
20 s
Maximum duration of start for too
long start
2 à 200 s
STALLED DELAY
0.2 s
Time delay to detect a locked rotor
after a start
0.2 to 2.0 s
REL.LONG S/ROT S
A B C D
Select the too long start and locked
rotor relays (51 LR)
See chap 4 to choose a relay
or to modify the assignment
REL.LONG S/ROT S
E F G
(relays D, E, F, G if option
available)
MAX NBR STARTS
Active
Choose Active for the maximum
number of starts function
Active or Inactive
MAX NBR STARTS
3
Maximum number of starts during
time delay
1 to 4