NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 32
Indice : g
RECLOSE PULSE
200 ms
Setting of the minimum duration of
reclosing pulse
100 to 500 ms
O/O INPUT
Input 1
Display of input assigned to the O/O
interlock position (CB closed)
No input, Input 1 to 8 (or 1 to
4 according option)
C/O Input
Input 2
Display of input assigned to the F/O
interlock position (CB open)
No input, Input 1 to 8 (or 1 to
4 according option)
LOCAL INPUT
No input
Display of input assigned to the LOCAL
operation mode
(Available if the communication
option is present and if the management of input(s)
number Local/distant is carried out with 2 digital
inputs)
No input, Input 1 to 8 (or 1 to
4 according option)
DISTANT INPUT
Input 4
Display of input assigned to the
DISTANT operation mode
(Available if the
communication option is present)
No input, Input 1 to 8 (or 1 to
4 according option)
5.12 Disturbance menu
This menu is used to configure the parameters of the disturbance recording.
MAIN MENU
PERTURBOGRAPHY
Parameters of the disturbance
recording function
PRE-TIME
30 period(s)
Set pre time
1 to 52 periods
PERTURBO. INPUT
E5
Display of input assigned to the
external disturbance recording
triggering
No input, Input 1 to 8 (or 1
to 4 according option)
REL. DISTURB.
A B C D
Select relay to assign to
disturbance recording trip
(Available from V3.00 Firmware )
See chap 4 to choose a
relay or to modify the
assignment
REL. DISTURB.
E F G
(relays D, E, F, G if option
available)