RELAY C.B. FAULT
A B C D
Select relay to assign to the circuit
breaker failure function
See chap 4 to choose a relay
or to modify the assignment
RELAY C.B. FAULT
E F G
(relays D, E, F, G if option
available)
RELAY DISC. L/D
A B C D
Select relay to assign to the
local/distant discrepancy function
(remote control in service)
RELAY DISC. L/D
E F G
(relays D, E, F, G if option
available)
I AVERAGE
in 30 mn
Adjustment of the time for
calculation of average values and
maximeters
5 to 60 min
NB OF INPUTS L/D
1 input
Number of input(s), configurable for
the management of the
Local/Distant mode
1 or 2
5.14.2 Operation menu (since V3.00 firmware)
MAIN MENU
OPERATION
Operating parameters to be defined
at commissioning
LANGUAGE
English
Choice of the language used locally
by protection
French, English, Italian or
Spanish
ADJUST LCD
200
Adjustment of the angle of vision of
the LCD display
70 to 255
I NOMINAL PRIM.
1000 A
Set the value of the phase primary
rated current of the CTs
1 to 10000 A
Io NOMINAL PRIM.
100 A
Set the value of the earth primary
rated current of the CT
1 to 10000 A
SET 2 INPUT
E6
Display of input assigned to setting
group 2
No input, Input 1 to 8 (or 1 to 4
according option)