This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM800 – NPM800R
NPM800RE
Date : 05/2013
Edition :30/01/2014
Folio : 50
Indice : g
8.3 NPM800 connections
Connections
Location
Characteristics
Modbus® or IEC870-5-103
Communication
RS485-1
RS485-2
Screw terminal block. Section of wire 0.6 to 2.5
mm²
A
Screw terminal block not used
Digital inputs
B
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Relays
C and D
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Auxiliary supply
AUX
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Relays
(optional board)
E and F
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Digital inputs
(optional board)
G
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Connection of the CTs
IA to IO
4 mm ring type terminal. Section of wire
≤
6 mm²
For CTs inputs, take care to follow the rotating sense of phases and the direction of the
connection of each phase during the wiring.
8.4 NPM800 diagram
The diagram is available under the reference S 38024.
8.5 NPM800 connection of the current inputs
Connection is done by 6mm² ring terminals for M4 screw. It is identical for all the variants of
inputs:
♦
Phases CT 1A or 5A
♦
Earth-fault CT 1A or 5A or CT Ring.