3. First use
When powering the relay, the displays below can appear. The recommended action allows
starting the parameter setting of protection.
3.1 Default screen
In absence of a fault, the protection displays the phase 1 current measurement in HV value.
CURRENT I1
0.0 A
3.2 Presence of a fault or an alarm
If a fault or alarm occurs, a message indicates the type of fault.
TRIP
PHASE FAULT
This message disappears at once after acknowledgement of the fault and is replaced by the
following message.
TRIP PH FAULT S
10/12 16:38.15 R
This message remains until the acknowledgement of the fault by the User.
Note: if the mode «simplified recording of events" is not chosen, the display will be as
follows:
TRIP PH FAULT S
17/08 14:22:28 R
INST PH FAULT S
17/08 14:22:28 R
TRIP PH FAULT A
17/08 14:22:27 R
TRIP PH FAULT A
17/08 14:22:26 R
3.3 Acknowledgment of latching output relays – ANSI 86
For the Firmware s
≥
V2.20 and < V3.00, see the « Counters » menu.
For the Firmware s > V3.00, see the « Maintenance » menu.