QD-ENG-40 REV.3
- 11 -
MAINTENANCE:
- continued -
2.
Condensate Management System
: The condensate management system should be
checked periodically for scale, sludge and debris that may cause the system to fail. The type
of environment will determine the frequency of required maintenance.
Maintenance of the condensate management system will require removal of electrical power
from the Ice Qube system and removal of the cover
. Please contact Ice Qube before
removing the cover during the warranty period.
*** CAUTION ***
Electrical wires are connected from the cover to the base.
Removing the cover will allow access to the primary condensate management pan, which is
located below the evaporator. Inspect the condensate pan and the drain nipple for signs of
scale, sludge or debris that may prevent water flow through the nipple. To clean the debris
from the pan, use a clean absorbent cloth or shop-vac. Nipples may be cleaned using a ¼
inch tubing brush, then flush with clean water.
Also inspect the neoprene tubing that is attached to the nipples on the condensate
management system. Replace the tubing if it appears to have internal build-up or has become
brittle.
NOTE: If there is a secondary condensate management pan, maintenance will
need to be performed in the same manner as explained above.
After all debris has been removed from the system, replace the cover onto the unit – being
careful not to damage the wiring connecting the cover to the base.
3.
Cooling system cabinet
: The cooling system cabinet may also need to be cleaned
occasionally. To clean the system cabinet, simply wipe it with a damp, lint free cloth. A mild
soap solution may be used if necessary.
All current documentation and cut out templates can be found on our website at
www.iceqube.com