FND Timeouts
The FND board has the following non-adjustable
timeouts:
•
When the 'ICE/OFF/WASH' switch is moved from
'ICE' to 'OFF' the ice machine will not stop until the
current freeze/harvest cycle is completed. This can
be overridden by initiating a forced harvest. Refer to
•
The maximum freeze time is 65 minutes. Once the
machine's freeze time exceeds 65 minutes, 3
consecutive times, it will trip Error Code 11.
•
The maximum harvest time is 5 minutes. Once the
machine's harvest time exceeds 5 minutes, 3
consecutive times, it will trip Error Code 12.
•
The maximum water fill is 5 minutes. Once the
machine's water fill time exceeds 5 minutes, it will
trip Error Code 15.
50
Summary of Contents for IM Series
Page 1: ...Revision Date 1 24 22 IM Series Air Water Remote Ice Machines Technician s Handbook ...
Page 2: ......
Page 3: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 9: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 15: ...THIS PAGE INTENTIONALLY LEFT BLANK 14 ...
Page 17: ...How to Read a Serial Number Full Serial Number 16 ...
Page 35: ...THIS PAGE INTENTIONALL Y LEFT BLANK 34 ...
Page 48: ...Flexible Numeric Display FND Functions 47 ...
Page 93: ...THIS PAGE INTENTIONALLY LEFT BLANK 92 ...
Page 106: ...Testing the water level sensor Before S N Starting With VC 105 ...
Page 134: ...SERVICE REMOTE RECOVERY EVACUATION CONNECTIONS 133 ...
Page 145: ...THIS PAGE INTENTIONALLY LEFT BLANK 144 ...
Page 155: ...THIS PAGE INTENTIONALLY LEFT BLANK 154 ...
Page 157: ...Wiring Diagram 156 ...
Page 158: ...PCB Layout 157 ...
Page 159: ...PCB Dip Switches 158 ...
Page 161: ...SPACE FOR TECHNICIAN S NOTES ...
Page 162: ...SPACE FOR TECHNICIAN S NOTES ...
Page 163: ...SPACE FOR TECHNICIAN S NOTES ...
Page 164: ...SPACE FOR TECHNICIAN S NOTES ...
Page 165: ......