Tip 1:
Error Code 11 Potential Causes
Ice thickness probe not
sensing water contact after 65
minutes 3 consecutive times.
Water:
•
Is there sufficient water supply?
•
Is the water pressure below 20psi?
•
Is the water level sensor scaled up or giving a false full level
reading?
•
Does the water pump have power but it’s not running?
•
Is the water distribution tube scaled up?
•
Is the was dump valve dirty or stuck open?
Ice Thickness Sensor:
•
Is the ice thickness sensor adjusted too far out?
•
Is the ice thickness sense faulty and not reading properly?
Refrigerant:
•
Is the system undercharged?
•
Is the TXV starving the evaporator?
•
Is the hot gas valve leaking?