MILD SYSTEM CONTAMINATION CLEANUP
PROCEDURE
1. Replace any failed components.
2. If the compressor is good, change the oil.
3. Replace the liquid line drier.
NOTE: If the contamination is from moisture, use heat
lamps during evacuation. Position them at the compressor,
condenser and evaporator prior to evacuation. Do not
position heat lamps too close to plastic components, or
they may melt or warp.
4. Follow the normal evacuation procedure, except
replace the evacuation step with the following:
A. Pull vacuum to 1000 microns. Break the vacuum
with dry nitrogen and sweep the system.
Pressurize to a minimum of 5 psig.
B. Pull vacuum to 500 microns. Break the vacuum
with dry nitrogen and sweep the system.
Pressurize to a minimum of 5 psig.
C. Change the vacuum pump oil.
D. Pull vacuum to 500 microns. Run the vacuum
pump for 1/2 hour on self-contained models, 1
hour on remotes.
NOTE: You may perform a pressure test as a preliminary
leak check. You should use an electronic leak detector after
system charging to be sure there are no leaks.
5. Charge the system with the proper refrigerant to the
nameplate charge.
6. Operate the ice machine.
144
Summary of Contents for WU-0100A
Page 1: ...Undercounter Ice Machines Technician s Handbook Revision Date 1 24 22...
Page 2: ......
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...16 How to Read a Serial Number Full Serial Number...
Page 154: ...WU 0100 WIRING DIAGRAM Self Contained Air cooled 153...
Page 155: ...IC 0170 IU 0170 IC 0220 IU 0220 WIRING DIAGRAM Self Contained Air cooled 154...
Page 156: ...Printed Circuit Bards PCB WU 0100 PCB 155...
Page 161: ...SPACE FOR TECHNICIAN S NOTES...
Page 162: ...SPACE FOR TECHNICIAN S NOTES...
Page 163: ...SPACE FOR TECHNICIAN S NOTES...
Page 164: ...SPACE FOR TECHNICIAN S NOTES...
Page 165: ......