Adjustment and control system
32
ACCESS PATH
:
→
OFFSET AND SCALES
No.
Parameter Description
Reading level
Writing level
Visibility Conditions
08.01 Pressure value at 4 mA
SERVICE
SERVICE
Always
08.02 Pressure value at 20 mA
SERVICE
SERVICE
Always
08.03 Pressure offset
SERVICE
SERVICE
Always
08.04
TDS
value at 4 mA
SERVICE
SERVICE
If the
TDS
sensor is enabled
08.05
TDS
value at 20 mA
SERVICE
SERVICE
If the
TDS
sensor is enabled
08.06
TDS
offset
SERVICE
SERVICE
If the
TDS
sensor is enabled
08.07 Level Offset
SERVICE
SERVICE
If the level sensor is enabled
08.08 Flue gas temperature offset
SERVICE
SERVICE
If the flue gas temperature probe is
enabled
08.09 Ambient temperature offset
SERVICE
SERVICE
If the ambient temperature probe is
enabled
08.12 Steam flow pressure value at 4 mA
SERVICE
SERVICE
If the steam control valve is enabled
08.13 Steam flow pressure value at 20 mA
SERVICE
SERVICE
If the steam control valve is enabled
08.14 Steam delivery pressure offset
SERVICE
SERVICE
If the steam control valve is enabled
08.15 Cascade manifold pressure value at 4 mA
SERVICE
SERVICE
If the cascade control is enabled
08.16 Cascade manifold pressure value at 20 mA
SERVICE
SERVICE
If the cascade control is enabled
08.17 Cascade manifold pressure offset
SERVICE
SERVICE
If the cascade control is enabled
08.18 Pump flow pressure value at 4 mA
SERVICE
SERVICE
If the pump flow pressure probe is
enabled
08.19 Pump flow pressure value at 20 mA
SERVICE
SERVICE
If the pump flow pressure probe is
enabled
08.20 Pump flow pressure offset
SERVICE
SERVICE
If the pump flow pressure probe is
enabled
08.21 ECX 1 water inlet temperature offset
SERVICE
SERVICE
If the probe is enabled
08.22 ECX 1 water outlet temperature offset
SERVICE
SERVICE
If the probe is enabled
08.23 ECX 1 water meter pulse value (water delivery)
SERVICE
SERVICE
If the meter is enabled
08.24 ECX 2 water inlet temperature offset
SERVICE
SERVICE
If the probe is enabled
08.25 ECX 2 water outlet temperature offset
SERVICE
SERVICE
If the probe is enabled
08.26 ECX 2 water meter pulse value
SERVICE
SERVICE
If the meter is enabled
08.27 ECX 1 flue gas inlet temperature offset
SERVICE
SERVICE
If the probe is enabled
08.28 ECX 2 flue gas outlet temperature offset
SERVICE
SERVICE
If the probe is enabled
08.29 Make-up water meter pulse value
SERVICE
SERVICE
If the meter is enabled
08.30 Gas meter pulse value
SERVICE
SERVICE
If the meter is enabled
08.31
Burner maximum power (kW)
Power is estimated based on the output modulation signal,
unless the feedback on IC1 input expansion 1 is present. In this
case, the feedback will be considered.
SERVICE
SERVICE
Always
08.32 First stage burner power (kW)
SERVICE
SERVICE
Always
08.34 Estimated CO
2
(%)
SERVICE
SERVICE
Always
08.35 % O
2
at 4 mA
SERVICE
SERVICE
If the oxygen sensor is enabled
08.36 % O
2
at 20 mA
SERVICE
SERVICE
If the oxygen sensor is enabled
08.37 CO
2
offset %
SERVICE
SERVICE
If the oxygen sensor is enabled